Page 71
ADDENDUM FOR ALL PROVINCES OF CANADA
See below for venting in all provinces of Canada. Lennox approves the following termination for use in all provinces of 
Canada.
C
12”
D
B
A
2” (51MM)
Vent Pipe
3” (76MM)
Vent Pipe
12” (305 mm) Min. 12” (305 mm) Min.
6” (152 mm) Min.
24” (610 mm) Max.
6” (152 mm) Max.
6” (152 mm) Min.
24” (610 mm) Max.
6” (152 mm) Max.
A − Clearance above grade or
average snow accumulation
B − Horizontal separation between
intake and exhaust
C − Exhaust pipe length
D − Wall support distance from top
of each pipe (intake/exhaust)
NOTE −  Flue gas may be acidic and may adversely affect some building materials. If flue gases impinge
on the building materials, a corrosion−resistant shield should be used to protect the wall surface. The
shield should be constructed using wood, sheet metal or other suitable material. All seams, joints, cracks,
etc. in affected area, should be sealed using an appropriate sealant.
Per: Saskatchewan Code of Practice