FLEXYII_WSHP-IOM-1307-E - 71 -
Function
The Climatic
TM
60 has free inputs / outputs on the main board BM60 and the expansion board BE60 to
offer different possibilities to customize input / output for remote control of the unit.
Description
Free customized inoputs / outputs number depends on added option. Without any option, expansion
board BE60 is available with DCBO option.
Below, "not always available" means that some inputs/outputs could be used by options. Refer to the
electrical wiring diagram or to the CL60_IOM.
Digital outputs (dry contacts NO)
Maximum 2 free output contacts on BM60 :
Maximum 4 free output contacts on BE60
Functions can be set among followings:
Alarm, Dirty filters or missing
Alarm, Circuit (Compressor)
Alarm, Electrical heaters
Alarm, Supply to low (Freeze protection)
Circuit, Defrosting cycle requested or
activated (Compressor)
Control, Heating mode activated
Control, Dead zone mode activated
Control, Cooling mode activated
Schedule, Mode A activated
Schedule, Mode B activated
Schedule, Mode C activated
Schedule, Mode D activated
Schedule, Mode BMS activated
Schedule, Zone 0 activated
Schedule, Zone 1 activated
Schedule, Zone 2 activated
Schedule, Zone 3 activated
Schedule, Zone 4 activated
Schedule, Zone 5 activated
Schedule, Zone 6 activated
Analog inputs (NTC probe or 4/20mA signal)
No analog input on BM60 :
Maximum 4 free analog inputs on BE60
Functions can be set among followings:
Power of the unit (ON/OFF)
BMS, temperature (NTC) reading for BMS
BMS, relative humidity (4-20mA) reading for
BMS
Control set point, swift of the value (4mA=-5K,
20mA=+5K)
Fresh air set point, value (4mA=0%,
20mA=100%)
Speed blower set point, value (4mA=low level,
20mA=nominal level)
Control, outside temperature by 4-20mA
sensor
Control, room temperature by 4-20mA sensor
Control, outside relative humidity by 4-20mA
sensor
Control, room relative humidity by 4-20mA
sensor