EasyManuals Logo
Home>Lennox>Heat Pump>HP21

Lennox HP21 User Manual

Lennox HP21
53 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #5 background imageLoading...
Page #5 background image
Page 5
D−Hard Start Relay K31 (single-phase only)
All single-phase HP21 units are equipped with a hard start
relay located in the unit control box which controls the op-
eration of the compressor starting circuit. The relay is normally
closed when the compressor (contactor K1) is de-energized.
Capacitor (C7) is connected in series to a set of normally
closed K31 contacts and assists the compressor in starting.
When K1 energizes, the compressor immediately begins start-
up. K31 remains de-energized during compressor start-up and
the start capacitor (C7) remains in the circuit. As the compres-
sor gains speed K31 is energized by electromotive forces
generated by the compressor. When K31 energizes, its con-
tacts open to take the start capacitor out of the circuit.
E−Terminal Strip TB15
All HP21 units are equipped with a low voltage terminal
strip located in the unit control box for making up thermo-
stat wiring connections (refer to figure 2).
F−Compressor B1
See ELECTRICAL DATA or compressor nameplate for
specifications. Figure 3 shows the compressor terminal
box. All compressors are equipped with internal pressure
relief valves set at 450+50 psig. Compressors in all units
use insertion type crankcase heaters which are regulated
by relays in the HP21.
FIGURE 3
T3 T8 T1 T7
SINGLE
PHASE
T2
S1 S2
TYPICAL TWO-SPEED COMPRESSOR
TERMINAL BOX
COPELAND SINGLE-PHASE SHOWN
G−Outdoor Fan Motor B4
The specifications table on page 1 of this manual shows the
specifications of outdoor fans used in all HP21 units. In
single-phase units, the outdoor fan is controlled by the
compressor contactor and is de−energized when the de-
frost relay is energized. In three-phase units, the outdoor
fan is controlled by contactor K10 and is de-energized
when the defrost relay is energized. See figure 4 if outdoor
fan motor replacment is necessary.
FAN GUARD
Condenser fan
and motor
Wiring
Drip loop
FIGURE 4
1/4"
H−High Pressure Limit S4
All units are equipped with a high pressure limit mounted on
the compressor discharge line. The switch can be manual-
ly reset and has a cutout" point of 410+10 psig. The switch
is electrically connected in series with crankcase thermo-
stat S40 in the two-speed control’s safety circuit. When
tripped, the TSC interrupts unit operation. If the high pres-
sure switch trips" three times within the same thermostat
demand, the two-speed control locks out and the contactor
cannot energize.
Although the high pressure limit must be reset manually, if
the two-speed control is locked out it must be reset before
the unit can operate. To reset the control, break and re-
make thermostat demand.
I−Crankcase Thermostat S40
Crankcase thermostat S40 is electrically connected in se-
ries with high pressure limit S4 in the two-speed control’s
safety circuit. It is used in all units to monitor the tempera-
ture of the compressor. The switch is a N.C. SPST
belly-band" thermostat strapped to the compressor.
The switch is factory preset to trip at 190°F+5°F on a tem-
perature rise. When tripped, the TSC interrupts unit
operation. The crankcase thermostat automatically resets
when the compressor crankcase drops below 110°F+7°F. If
the crankcase thermostat trips" three times within the
same thermostat demand, the two-speed control locks out
and the contactor cannot energize. If the two-speed control
is locked out it must be reset before the unit can operate. To
reset the control, break and remake thermostat demand.

Table of Contents

Other manuals for Lennox HP21

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox HP21 and is the answer not in the manual?

Lennox HP21 Specifications

General IconGeneral
BrandLennox
ModelHP21
CategoryHeat Pump
LanguageEnglish

Related product manuals