Page 38
2- Electronic thermostat
Any two stage heat / two stage cool electronic ther
mostat may be used.
3- Honeywell T7300 thermostat (60L59)
The Honeywell T7300 thermostat is a programmable, in
ternal or optional remote temperature sensing thermo
stat. The T7300 provides occupied and unoccupied
changeover control.
J-Smoke Detectors A171 and A172
Photoelectric smoke detectors are a field-installed option.
The smoke detectors can be installed in the supply air sec
tion (A172), return air section (A171), or in both the supply
and return air sections.
K-LP / Propane Kit
KGA092/150 units require a natural to LP /propane kit.
The kit includes one LP spring conversion kit, up to eleven
burner orifices and three stickers. For more detail refer to the
natural to LP gas changeover kit installation instructions.
L-Drain Pan Overflow Switch S149 (optional)
The overflow switch is used to interrupt cooling operation
when excessive condensate collects in the drain pan. The
N.O. overflow switch is controlled by K220 and DL46 re
lays, located in the unit control panel. When the overflow
switch closes, 24VAC power is interrupted and after a five-
second delay unit compressors are de-energized. Once
the condensate level drops below the set level, the switch
will open. After a five-minute delay the compressor will be
energized.