KGB SERIES
Service Literature
2 to 7-1/2 ton
7 to 26 kW
May 2020
KGB024 through 090
The KGB packaged gas units are available in standard
cooling efficiency (024, 030, 036, 048 060, 072, 074 and
090). Cooling capacities range from 2 to 7-1/2 tons (7 to
26kW).
KGB024, 030, 036, 048, 060, 072, 074 units are avail
able in 65,000 BTUH heat capacity /KGB036, 048, 060,
072, 074 and 090 units are available in 108,000 BTUH
(105,000 BTUH in earlier built units ) heat capacity.
KGB048, 060, 072, 074 and 090 units are available in
150,000 BTUH (44 kW) heat sizes. Two stage heat is
available in units with 108,000 (105,000 in earlier built
units) and 150,000 BTUH capacities. Gas heat sections
are designed with aluminized steel tube heat exchang
ers.
Information contained in this manual is intended for use by
qualified service technicians only. All specifications are
subject to change. Procedures outlined in this manual are
presented as a recommendation only and do not super
sede or replace local or state codes.
If the unit must be lifted for service, rig unit by attaching four
cables to the holes located in the unit base rail (two holes at
each corner). Refer to the installation instructions for the
proper rigging technique.
WARNING
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, person
al injury or loss of life. Installation and service must
be performed by a licensed professional installer (or
equivalent), service agency or the gas supplier.
WARNING
Electric shock hazard. Can cause injury
or death. Before attempting to perform
any service or maintenance, turn the
electrical power to unit OFF at discon
nect switch(es). Unit may have multiple
power supplies.
CAUTION
As with any mechanical equipment, contact with
sharp sheet metal edges can result in personal in
jury. Take care while handling this equipment and
wear gloves and protective clothing.
CAUTION
Electrostatic discharge can affect electronic
components. Take precautions during unit instal
lation and service to protect the unit's electronic
controls. Precautions will help to avoid control
exposure to electrostatic discharge by putting
the furnace, the control and the technician at the
same electrostatic potential. Neutralize electro
static charge by touching hand and all tools on an
unpainted unit surface, such as the gas valve or
blower deck, before performing any service pro
cedure.
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
Table of Contents
Options Page 2.......................
Specifications Page 6..................
Spec. Gas Heat / High Altitude Page 13...
Blower Data Page 14...................
Electrical Data Page 31.................
I Unit Components Page 35.............
II Placement and Installation Page 48.....
III Start Up Operation Page 48...........
IV Charging Page 50...................
V System Service Checks Page 60.......
VI Maintenance Page 62................
VII Accessories Page 63................
VIII Diagrams Page 69..................

Table of Contents

Question and Answer IconNeed help?

Do you have a question about the Lennox KGB036S4B and is the answer not in the manual?

Lennox KGB036S4B Specifications

General IconGeneral
SEER14
HSPF8.2
Refrigerant TypeR-410A
Voltage (V)208/230
Phase1
Cooling Capacity (BTU)36000
Heating Capacity (BTU)36000
SEER Rating14
HSPF Rating8.2

Summary

ELECTROSTATIC DISCHARGE (ESD)

SPECIFICATIONS - DIRECT DRIVE BLOWER

SPECIFICATIONS - BELT DRIVE BLOWER

Cooling Performance

Cooling capacity, airflow, and efficiency for belt drive units.

Refrigerant Charge

Refrigerant type and charge details for belt drive models.

Electrical Characteristics

Electrical requirements for belt drive units.

SPECIFICATIONS - STANDARD GAS HEAT

SPECIFICATIONS - LOW NOx GAS HEAT

BLOWER DATA

ELECTRICAL DATA

DIRECT DRIVE ECM - 2 TON | 2.5 TON

Electrical specs for 2 and 2.5 Ton ECM units.

DIRECT DRIVE PSC - 3 TON

Electrical specs for 3 Ton PSC units.

DIRECT DRIVE PSC - 5 TON

Electrical specs for 5 Ton PSC units.

DIRECT DRIVE ECM - 3 TON | 4 TON | 5

Electrical specs for 3, 4, and 5 Ton ECM units.

DIRECT DRIVE PSC - 4 TON

Electrical specs for 4 Ton PSC units.

I-UNIT COMPONENTS

B-Cooling Components

Compressor B1

Details compressor specifications and safety warnings.

SAFETY AND CONTROL COMPONENTS

Refrigerant System Safety Switches

Details freezestat, high pressure, low ambient, and low temp switches.

DETERMINING UNIT CFM

Single-Speed, Direct Drive Blowers

How to determine CFM for single-speed direct drive blowers.

Belt Drive Blowers

How to determine CFM for belt drive blowers.

FIELD-ADJUSTABLE BLOWER SPEEDS

DIRECT DRIVE 208230 V

How to adjust blower speeds for 208/230V direct drive units.

DIRECT DRIVE 460575 V

How to adjust blower speeds for 460/575V direct drive units.

BLOWER BELT ADJUSTMENT

BELT ADJUSTMENT AND INSTALLATION

GAS HEAT COMPONENTS

Heat Exchanger

Description and illustration of the heat exchanger.

Burner Box Assembly

Details on burner assembly, including burners and orifices.

GAS HEAT COMPONENTS - SAFETY AND CONTROL

High Temperature and Flame Limit Switches

Details high temp limits and flame sensing components.

Combustion Air and Gas Valves

Information on inducer motor, capacitor, and gas valves.

Spark Electrode (Ignitor)

Details on the spark electrode assembly and its function.

FLAME SENSING AND INSTALLATION

Flame Sensor

Description of the flame sensor and its function.

UNIT OPERATION AND SAFETY

Smoke Potential and Gas Safety

Warnings regarding smoke and gas handling.

Placing Unit In Operation

Step-by-step procedure for starting the unit.

Gas Valve Operation

Instructions for operating the gas valve.

COOLING START-UP AND SAFETY

Cooling Start-up Procedures

Steps for initiating unit cooling operation.

Safety or Emergency Shutdown

Procedures for safely shutting down the unit.

REFRIGERANT CHARGING

Refrigerant Charge and Check

Procedures for checking and charging refrigerant.

REFRIGERANT CHARGING DATA

KGBKCB024 Normal Operating Pressures

Normal operating pressures for KGB/KCB024 models.

KGBKCB030 Normal Operating Pressures

Normal operating pressures for KGB/KCB030 models.

KGBKCB036 Normal Operating Pressures

Normal operating pressures for KGB/KCB036 models.

KGBKCB048 Normal Operating Pressures

Normal operating pressures for KGB/KCB048 models.

KGBKCB060 Normal Operating Pressures

Normal operating pressures for KGB/KCB060 models.

KGBKCB 072 H Normal Operating Pressures

Normal operating pressures for KGB/KCB072H models.

KGBKCB 074 S & H Normal Operating Pressures

Normal operating pressures for KGB/KCB074S&H models.

KGBKCB 090 Normal Operating Pressures

Normal operating pressures for KGB/KCB090 models.

KGBKCB 024 Charging Curves

Charging curves for KGB/KCB024 models.

KGBKCB030 Charging Curves

Charging curves for KGB/KCB030 models.

KGBKCB036 Charging Curves

Charging curves for KGB/KCB036 models.

KGBKCB048 Charging Curves

Charging curves for KGB/KCB048 models.

KGBKCB060 Charging Curves

Charging curves for KGB/KCB060 models.

KGBKCB 072 Charging Curves

Charging curves for KGB/KCB072 models.

KGBKCB074 S & H Charging Curves

Charging curves for KGB/KCB074S&H models.

KGBKCB 090 Charging Curves

Charging curves for KGB/KCB090 models.

REFRIGERANT CHARGE VERIFICATION

FinTube Coil Charge Check

Procedures for checking refrigerant charge on Fin/Tube coils.

Approach Method (FinTube Coil)

Verifying refrigerant charge using the approach method.

SYSTEM SERVICE CHECKS

ECONOMIZER CONTROLS

ECONOMIZER AND VENTILATION CONTROL

ECONOMIZER OPERATION MODES

WIRING DIAGRAMS AND SEQUENCE OF OPERATION

SEQUENCE OF OPERATION

GAS HEAT SEQUENCE OF OPERATION

THERMOSTAT WIRING AND OPERATION

ECONOMIZER SYSTEM OPERATION

OUTDOOR AIR DAMPER AND ECONOMIZER SEQUENCE