N-Hot Gas Reheat Start-Up and Operation
General
Hot gas reheat units provide a dehumidifying mode of
operation. These units contain a reheat coil adjacent
refrigerant routing.
L14 Reheat Coil Solenoid Valve
reheat valve is energized and refrigerant is routed to the
reheat coil.
Reheat Setpoint
the indoor relative humidity falls below or the digital output
deenergizes. Turn the knob on the dehumidistat to adjust
the setpoint.
Check-Out
Test hot gas reheat operation using the following
procedure.
1 - Make sure reheat is wired as shown in wiring
section.
2 -
compressor 2 should be operating.
3 -
setpoint knob ABOVE indoor relative humidity. The
deenergize.
Default Reheat Operation
TABLE 25
Demands
Operation
Compressor 2 Cooling*
Compressor 1 Cooling &
Compressor 2 Cooling**
will operate.
and compressor 1 will operate.
REHEAT MODE REFRIGERANT ROUTING
EXPANSION
VALVES
REFRIGERANT
CIRCUIT 1
REFRIGERANT
CIRCUIT 2
REHEAT
VALVE
CHECK
VALVE
CONDENSER COIL
092/102 STG 1
120/150 STG 2
092/102 STG 2
120/150 STG 1
DRAWING SHOWS
102/120
FIGURE 40