EasyManuals Logo

Lennox KHA SERIES User Manual

Lennox KHA SERIES
49 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #22 background imageLoading...
Page #22 background image
Page 22
I−UNIT COMPONENTS
The KHA unit parts arrangement are shown in figure 1. All
L1, L2 and L3 wiring is color coded; L1 is red, L2 is yellow
and L3 is blue. See wiring diagrams in the back of this manu-
al for complete call out of components.
A−Control Box Components
KHA control box components are shown in figure 2. The
control box is located in the upper portion of the compres-
sor compartment.
1−Terminal Strip TB1
All indoor thermostat connections will be to TB1 located in
the control box.
2−Transformer T1
All KHA series units use a single line voltage to 24VAC
transformer mounted in the control box. Transformer
supplies power to control circuits in the unit. The trans-
former is rated at 70VA and is protected by a 3.5 amp cir-
cuit breaker (CB8). The 208/230 (Y) voltage transform-
ers use two primary
voltage taps as shown
in figure 3, while 460
(G) and 575 (J) voltage
transformers use a
single primary voltage
tap.
3−Outdoor Fan Capacitor C1 (Y, G, J & M)
Fan capacitors C1 is used to assist in the start up of con-
denser fan motor B4. Capacitor ratings will be on outdoor fan
motor nameplate.
4−Dual Capacitor C12 (Single Phase)
A single dual capacitor is used for both the outdoor fan and
compressor (see unit diagram). The fan side and the compres-
sor side have different MFD ratings. See side of capacitor for
ratings,.
5−Compressor Contactor K1
K1 is a 24V line voltage contactor used to energize the
compressor and in some cases (P and Y voltage) con-
denser fan in response to thermostat demand. Single
phase units use single−pole double break contactors
and three phase units use three−pole double break con-
tactors.
6−Low Ambient Kit Relay K58
(option used with S11 low ambient switch)
Low ambient relay K58 is a N.C.DPDT relay with a 24V
coil wired in parallel with reversing valve L1. When L1 is
energized in the cooling cycle, K58 is also energized
opening K58−1. Therefore, K58−1 is always closed dur-
ing heating demand bypassing S11. This allows the fan
to operate during the heating demand and cycle during
the cooling demand.
7−Blower Contactor K3
Blower contactor K3 is used in all units. K3 has a 24V coil used
to energize the indoor blower motor in response to blower de-
mand. In single phase units K3 is a single−pole contactor and in
three phase units K3 is a two−pole contactor.
8−Transfer Relay K8
K8 is a two−pole relay with a 24V coil used to de−energize the
reversing valve during a heat call. On a first stage heat call
K8−1 closes de−energizing the reversing valve and K8−2 closes
energizing Y1 on the CMC1 board. Without K8 the reversing
valve would remain energized at all times.
9−Outdoor Fan Relay K10 G, J & M Voltage
Outdoor fan relay K10 is a DPDT relay switch with a 24VAC
coil. K10 energizes condenser fan motor B4 in response to a
heating or cooling demand.
10−Transformer T4 (J voltage)
All (J) 575 voltage units use transformer T4 mounted in the
control box. T4 is a line voltage to 460V to power the indoor
blower. It is connected to line voltage and is powered at all
times.
FIGURE 3
PINK GRAY
ORANGE GRAY
230 VOLTS
208 VOLTS
PRIMARY
SECONDARY
208/230V TRANSFORMER

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox KHA SERIES and is the answer not in the manual?

Lennox KHA SERIES Specifications

General IconGeneral
BrandLennox
ModelKHA SERIES
CategoryHeat Pump
LanguageEnglish

Related product manuals