EasyManua.ls Logo

Lennox LDT DUAL FUEL Series - Page 12

Lennox LDT DUAL FUEL Series
50 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 12
ELECTRICAL DATA 8.5 TON
Model No. LDT102H4E
1
Voltage - 60Hz 208/230V-3ph 460V-3ph 575V-3ph
Compressor 1

Rated Load Amps 12.9 7.1 4.6
Locked Rotor Amps  62 39
Compressor 2

Rated Load Amps 16 7.8 
Locked Rotor Amps 110  38.9
Outdoor Fan

 2.8 1.4 1.1
Total  2.8 2.2
Power Exhaust

Full Load Amps 2.4 1.3 1
   20
Indoor Blower
Motor
Horsepower   
Full Load Amps 8.7 4.7 4.1
2
Maximum
Overcurrent

Unit Only 60 30 20

Power Exhaust
60 30 20
3
Minimum
Circuit

Unit Only 48  19

Power Exhaust
 26 20

1
Extremes of operating range are plus and minus 10% of line voltage.
2
HACR type breaker or fuse.
3
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
ELECTRICAL DATA 10 TON
Model No. LDT122H4E
1
Voltage - 60Hz 208/230V-3ph 460V-3ph 575V-3ph
Compressor 1

Rated Load Amps 16.7 7.1 
Locked Rotor Amps 110  47.8
Compressor 2

Rated Load Amps 19.6 8.2 6.6
Locked Rotor Amps 136 66.1 
Outdoor Fan

 2.8 1.4 1.1
Total  2.8 2.2
Power Exhaust

Full Load Amps 2.4 1.3 1
   20
Indoor Blower
Motor
Horsepower   
Full Load Amps 8.7 4.7 4.1
2
Maximum
Overcurrent

Unit Only 70 30 

Power Exhaust
80  
3
Minimum
Circuit

Unit Only  27 22

Power Exhaust
61 28 23

1
Extremes of operating range are plus and minus 10% of line voltage.
2
HACR type breaker or fuse.
3
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.

Related product manuals