Page 27
THERMOSTAT DEMAND
COMBUSTION AIR BLOWER
GAS VALVE
IGNITION SPARK
BLOWER
IGNITION TRIAL
SECONDS0 30
ON
OFF
IGNITION CONTROL TIMING
30
30
HEATING
CYCLE
6 (+3.4, -2.0) SEC.
END OF
THERMOSTAT
DEMAND
123
42 SEC. 122 SEC.
FIGURE 16
         


immediately restart the ignition sequence and then lock
out if ignition is not gained after the third trial. See System

󰀨
a power failure. Upon restoration of gas and power, the
control will restart the ignition sequence and continue until

On a heating demand, the ignition control is energized by
      
30 to 40 seconds for the combustion air blower to vent
exhaust gases from the burners. When the combustion
air blower is purging the exhaust gases, the combustion
air prove switch is closing proving that the combustion air
blower is operating before allowing the ignition control to
energize. When the combustion air prove switch is closed
and the delay is over, the ignition control activates gas
        -

The combustion air blower continues to operate through-

do not ignite, the ignition control will attempt to ignite the
burners up to two more times. If ignition cannot be ob-
tained after the third attempt, the control will lock out. The
ignition control is not adjustable.
13-Balance Point Thermostat A526
       
+
When outdoor air temperature falls below setpoint, the
unit willoperate in gas heat mode. The balance point set-
point can be adjusted using the following mobile service





the setpoint can be adjusted. Weigh the comfort / cost

II-PLACEMENT AND INSTALLATION
Make sure the unit is installed in accordance with the in-
stallation instructions and all applicable codes. See ac-
cessories section for conditions requiring use of the op-

III-START UP - OPERATION
Refer to start-up directions and refer closely to the unit
wiring diagram when servicing. See unit nameplate for
minimum circuit ampacity and maximum fuse size.
A-Preliminary and Seasonal Checks
1 - Make sure the unit is installed in accordance with
the installation instructions and applicable codes.
2 -        
installed for loose connections. Tighten as required.
Refer to unit diagram located on inside of unit
control box cover.
3 - Check to ensure that refrigerant lines are in good
condition and do not rub against the cabinet or
other refrigerant lines.
4 - Check voltage at the disconnect switch. Voltage
must be within the range listed on the nameplate.
If not, consult the power company and have the
voltage corrected before starting the unit.
 Recheck voltage and amp draw with unit running. If
voltage is not within range listed on unit nameplate,
stop unit and consult power company. Refer to unit
nameplate for maximum rated load amps.
6 - Inspect and adjust blower belt (see section on

B-Heat Pump Start Up
Note - The outdoor air ambient temperature must be above
-
able heat pump operation. The balance point setpoint can
be adjusted using the following mobile service app menu

