12-Burner Control A3
WARNING
Shock hazard. Spark related components
contain high voltage which can cause
personal injury or death. Disconnect
power before servicing. Control is not
    
result. If control is inoperable, simply
replace the entire control.
The ignition controls are located in the heat section areas
below the compressors. The controls are manufactured
UTEC. See TABLE 4 for LED codes.
       
        
        
attempt sequence provides three trials for ignition before

After lockout, the ignition control automatically resets and
provides three more attempts at ignition. Manual reset af-
ter lockout requires breaking and remaking power to the
ignition control. See FIGURE 14 for a normal ignition se-


timings for the ignition controls are shown in FIGURE 16.
TABLE 4
LED Flashes Indicates
Slow Flash Control ok, no call for heat
Fast Flash Control ok, call for heat present.
󰀨 Internal control fault or no power
Steady On Failure Control internal failure
1 Flash Rollout switch open
2 Flashes
Limit open or lockout from to many
tries during a single heat demand
3 Flashes
Pressure switch open with inducer

󰀨
4 Flashes


losses.
 Flame sensed out of sequence
6 Flashes
Pressure switch closed with induc-
󰀨
7 Flashes Gas valve relay failure
8 Flashes
Lockout due to too many pressure
switch openings during one heat
demand
NORMAL IGNITION SEQUENCE - TIMINGS NOMINAL
THERMOSTAT DEMAND
COMBUSTION AIR BLOWER
GAS VALVE
IGNITION SPARK
BLOWER
IGNITION TRIAL
011053030SDNOCES
ON / CLOSED
OFF / OPEN
END OF
DEMAND
1
COMBUSTION AIR PROVE SWITCH
5 570
FIGURE 14
RETRIALS - IGNITION ATTEMPT SEQUENCE - TIMINGS NOMINAL
THERMOSTAT DEMAND
COMBUSTION AIR BLOWER
GAS VALVE
IGNITION SPARK
BLOWER
IGNITION TRIAL
SECONDS0 30 35 70
ON
OFF
65 100 105
WATCHGUARD
LOCKOUT
COMBUSTION AIR PROVE SWITCH
5
FIGURE 15