ELECTRICAL DATA 6.5 TON
Model No. LDT078H4E
1
Voltage - 60Hz 208/230V-3ph 460V-3ph 575V-3ph
Compressor 1

Rated Load Amps 12.9 7.1 4.6
Locked Rotor Amps  62 39
Compressor 2

Rated Load Amps  3.8 
Locked Rotor Amps 70 31 27
Outdoor Fan

 2.8 1.4 1.1
Total  2.8 2.2
Power Exhaust

Full Load Amps 2.4 1.3 1
   20
Indoor Blower
Motor
Horsepower   
Full Load Amps 8.7 4.7 4.1
2
Maximum
Overcurrent

Unit Only   20

Power Exhaust
  20
3
Minimum
Circuit

Unit Only 39 21 16

Power Exhaust
42 22 17

1
Extremes of operating range are plus and minus 10% of line voltage.
2
HACR type breaker or fuse.
3
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
ELECTRICAL DATA 7.5 TON
Model No. LDT092H4E
1
Voltage - 60Hz 208/230V-3ph 460V-3ph 575V-3ph
Compressor 1

Rated Load Amps 12.9 7.1 4.6
Locked Rotor Amps  62 39
Compressor 2

Rated Load Amps 13.7 6.1 4.8
Locked Rotor Amps 83.1 43 33
Outdoor Fan

 2.8 1.4 1.1
Total  2.8 2.2
Power Exhaust

Full Load Amps 2.4 1.3 1
   20
Indoor Blower
Motor
Horsepower   
Full Load Amps 8.7 4.7 4.1
2
Maximum
Overcurrent

Unit Only   20

Power Exhaust
60 30 20
3
Minimum
Circuit

Unit Only  23 17

Power Exhaust
47 24 18

1
Extremes of operating range are plus and minus 10% of line voltage.
2
HACR type breaker or fuse.
3
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.