EasyManua.ls Logo

Lennox LDT DUAL FUEL Series - System Service Checks; Refrigerant Charging Procedures; Subcooling Method for Charge Confirmation

Lennox LDT DUAL FUEL Series
50 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 30
IV- SYSTEMS SERVICE CHECKS
WARNING
Refrigerant can be harmful if it is inhaled. Refrigerant
must be used and recovered responsibly.
Failure to follow this warning may result in personal
injury or death.
A-Charging
WARNING-Do not exceed nameplate charge under
any condition.
This unit is factory charged and should require no further
adjustment. If the system requires additional refrigerant,
reclaim the charge, evacuate the system, and add re-
quired nameplate charge.
NOTE - System charging is not recommended below 60°F
(15°C). In temperatures below 60°F (15°C) , the charge
must be weighed into the system.
If weighing facilities are not available, or to check the

1 - Attach gauge manifolds to discharge and suction
lines. With the economizer disabled, operate the unit
in cooling mode at high speed using the following

-
ING STAGE 3
2 - Use a thermometer to accurately measure the
outdoor ambient temperature.
3 - 
TABLE 9 to determine normal operating pressures.
Pressures are listed for sea level applications at
80F dry bulb and 67F wet bulb return air.
4 - Compare the normal operating pressures to
the pressures obtained from the gauges. Minor
variations in these pressures may be expected due
󰀨󰀨
could mean that the system is not properly charged
or that a problem exists with some component in
the system. Correct any system problems before
proceeding.
 If discharge pressure is high, remove refrigerant
from the system. If discharge pressure is low, add
refrigerant to the system.
Add or remove charge in increments.
Allow the system to stabilize each time refrigerant
is added or removed.
6 - Use the following subcooling method along with the

TABLE 5

Outdoor
Coil
Entering

CIRCUIT 1 CIRCUIT 1
Dis-
charge
+10 psig
Suction

Discharge
+10 psig
Suction

 244 132 236 
 281 134 271 146
 322 136 309 148
 366 138  
  139 399 
 464 141 449 
TABLE 6

Outdoor
Coil
Entering

CIRCUIT 1 CIRCUIT 1
Dis-
charge
+10 psig
Suction

Discharge
+10 psig
Suction

  139  139
 286 140 291 140
 326 141 331 141
 370 142 376 143
 417 144 426 146
 468 146 481 148
TABLE 7

Outdoor
Coil
Entering

CIRCUIT 1 CIRCUIT 1
Dis-
charge
+10 psig
Suction

Discharge
+10 psig
Suction

  139  130
 283 142 296 133
 321 141 336 133
 370 146 389 138
 417 148  141
 469  492 144
TABLE 8

Outdoor
Coil
Entering

CIRCUIT 1 CIRCUIT 1
Discharge
+10 psig
Suction

Discharge
+10 psig
Suction

 248 126  
  128 293 127
 326 130 334 129
 372 132 379 131
 420  426 134
  139 477 137

Related product manuals