SPECIFICATIONS 10 TON | 12.5 TON
General Data Nominal Tonnage 10 Ton 12.5 Ton
󰀩 High High
Model Number LDT122H4E LDT150H4E
Blower Type DirectPlus™
ECM Direct Drive
with MSA
DirectPlus™
ECM Direct Drive
with MSA
Cooling
Performance
Gross Cooling Capacity - Btuh 121,000 141,000
1
Net Cooling Capacity - Btuh 118,000 136,000
AHRI Rated Air Flow - cfm 3400 4200
Total Unit Power - kW 9.9 12.6
1
 11.9 10.8
1
  14.3
Refrigerant Type R410A R410A
Refrigerant Charge
Furnished
Circuit 1 21 lbs. 8 oz. 22 lbs. 8 oz.
Circuit 2 20 lbs. 8 oz. 21 lbs. 8 oz.
Heating
Performance
1
Total High Heat Capacity - Btuh 114,000 128,000
¹ AHRI Rated Air Flow - cfm 3600 4200
Total Unit Power - kW  11
1
C.O.P.  
1
Total Low Heat Capacity - Btuh  73,000
  10.2
1
C.O.P.  2.10
Gas Heating Options Available - See page 227 
Compressor Type (number) 

Outdoor Coil  40.4 40.4
Tube diameter - in. 3/8 3/8
Number of rows 3 3
Fins per inch 20 20
Outdoor
Coil Fans
  
Motor rpm  
Total Motor watts 180-800 180-800
  
Number of blades 3 3
Total Air volume - cfm  
Indoor
Coil
 12.8 12.8
Tube diameter - in. 3/8 3/8
Number of rows 4 4
Fins per inch 14 14
Drain connection - Number and size 
Expansion device type Balanced Port Thermostatic Expansion Valve

Indoor
Blower
Nominal motor output  
Blower wheel nominal diameter x width - in.  
Filters  MERV 4, Disposable
Number and size - in. 
Electrical characteristics 
NOTE - Net capacity includes evaporator blower motor heat deduction. Gross capacity does not include evaporator blower motor heat deduction.