EasyManuals Logo

Lennox LRP14GE Series User Manual

Lennox LRP14GE Series
49 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #23 background imageLoading...
Page #23 background image
Page 23
Blower Data – LRP14HP
Model
No.
Blower Tap
Air Volume (cfm) at Various External Static Pressures - in. w.g.
0.1 0.2 0.30.4 0.50.6 0.
70
.8
LRP14HP24
Tap 1 (Fan Only) 680 590 550500 450 380 - -
--
- -
Tap 2 (Low Cooling) 890 830 800760 710 680 64
06
00
Tap 3 (High Cooling) 1000 960 930880 840 810 77
07
30
¹ Tap 4 (Low Electric Heat) 890 830 800760 - - -- - -- -
--
- -
¹ Tap 5 (High Electric Heat) - - -- - -- - -- - - 840 810 77
07
30
LRP14HP30
Tap 1 (Fan Only) 680 640 600570 530 490 - -
--
- -
Tap 2 (Low Cooling) 1100 1070 1050 1020 990 960 93
09
00
Tap 3 (High Cooling) 1180 1160 1130 1090 1070 1040 1010 960
¹ Tap 4 (Low Electric Heat) 1100 1070 1050 1020 - - -- - -- -
--
- -
¹ Tap 5 (High Electric Heat) - - -- - -- - -- - -1070 1040 1010 960
LRP14HP36
Tap 1 (Fan Only) 860 810 760710 660 590 55
04
90
Tap 2 (Low Cooling) 1300 1265 1235 1200 1165 1125 1015 1040
Tap 3 (High Cooling) 1475 1450 1420 1375 1345 1310 1275 1190
¹ Tap 4 (Low Electric Heat) 1300 1265 1235 1200 - - -- - -- -
--
- -
¹ Tap 5 (High Electric Heat) - - -- - -- - -1345 1310 1275 1190
LRP14HP42
Tap 1 (Fan Only) 800 720 640550 475 390 31
0-
- -
Tap 2 (Low Cooling) 1470 1410 1360 1300 1260 1210 1155 1095
Tap 3 (High Cooling) 1700 1650 1610 1575 1560 1480 1480 1390
¹ Tap 4 (Low Electric Heat) 1470 1410 1360 1300 - - -- - -- -
--
- -
¹ Tap 5 (High Electric Heat) - - -- - -- - -- - -1560 1480 1480 1390
LRP14HP48
Tap 1 (Fan Only) 1165 1075 1000 930 850 790 76
06
70
Tap 2 (Low Cooling) 1675 1630 1600 1540 1490 1440 1390 1300
Tap 3 (High Cooling) 1800 1770 1715 1690 1660 1610 1565 1500
¹ Tap 4 (Low Electric Heat) 1675 1630 1600 1540 - - -- - -- -
--
- -
¹ Tap 5 (High Electric Heat) - - -- - -- - -- - -1660 1610 1565 1500
LRP14HP60
Tap 1 (Fan Only) 1400 1320 1260 1200 1120 1060 98
09
00
Tap 2 (Low Cooling) 1920 1870 1820 1770 1720 1670 1450 1360
Tap 3 (High Cooling) 2240 2200 2140 2100 2060 2020 1980 1950
¹ Tap 4 (Low Electric Heat) 1920 1870 1820 1770 - - -- - -- -
--
- -
¹ Tap 5 (High Electric Heat) - - -- - -- - -- - -2060 2020 1980 1950
NOTE-Allairdataismeasuredexternaltounitwithoutair
1
Taps 4 and 5 are used with Optional Electric Heat. Refer to Electric Heat nameplate for proper heat tap selection.