Page 8
Electric Heat Capacities – LRP14HP and AC Models – LRP16HP
Input
Voltage
5 kW
7.5 kW 10 kW 15 kW 20 kW
No of
Steps
kW
input
Btuh
Output
No of
Steps
kW
input
Btuh
Output
No of
Steps
kW
input
Btuh
Output
No of
Steps
kW
input
Btuh
Output
No of
Steps
kW
input
Btuh
Output
208 1 3.8 12,800 1 5.6 19,200 1 7.5 25,600 1 11.2 38,200 1 15.0 51,200
22014.2 14,300 1 6.3 21,500 1 8.4 28,700 1 12.6 43,000 1 16.8 57,300
23014.6 15,700 1 6.9 23,500 1 9.2 31,300 1 13.8 47,000 1 18.4 62,700
240 1 5.0 17,100 1 7.5 25,600 1 10.0 34,100 1 15.0 51,200 1 20.0 68,200
Gas Heat Capacities – LRP14GE Only
Model 24, 30, 36 24, 30 36, 42 36, 42 48, 60 48, 60
Heating Input-054 -072 -072 -090 -108 -126
Heating
Capacity Btuh
Input 54,000 72,000 72,000 90,000 108,000 126,000
Output 43,800 58,400 58,400 72,900 87,500 102,100
1
AFUE 81% 81% 81% 81% 81% 81%
Temperature Rise - °F 30-60 40-70 35-65 40-70 40-70 45-75
Gas Supply Connection (FPT) - in. 1/2 1/2 1/2 1/2 1/2 1/2
Min. Recommended Gas Supply Pressure 5 in. w.g. Natural Gas, 11 in. w.g LPG / Propane
1
Annual Fuel Utilization Efficiency based on U.S. DOE test procedures and FTC labeling regulations.
Gas Heat Capacities – LRP16GE Only
Model 24, 36 36 48 60
Heating Input -072 -090 -108 -126
Heating
Capacity Btuh
First Stage - Input 54,000 67,500 81,000 94,500
Output 43,500 54,500 65,500 76,500
Second Stage Input 72,000 90,000 108,000 126,000
Output 58,000 73,000 88,000 102,000
1
AFUE 81% 81% 81% 81%
Temperature Rise - °F First Stage 35-45 35-45 45-55 45-55
Second Stage 45-55 45-55 50-60 50-60
Gas Supply Connection (FPT) - in. 1/2 1/2 1/2 1/2
Min. Recommended Gas Supply Pressure 5 in. w.g. Natural Gas, 11 in. w.g LPG / Propane
1
Annual Fuel Utilization Efficiency based on U.S. DOE test procedures and FTC labeling regulations.
Gas Heat Capacities – LRP14GN Only
Model 24, 30, 36 42, 48, 60
Heating Input -054 -072
Heating Capacity
Btuh
Input 54,000 72,000
Output 43,800 58,320
1
AFUE 81
1%
Temperature Rise - °F 30 - 60 25 - 55
Gas Supply Connection (FPT) - in. 1/
/2
Min. Recommended Gas Supply Pressure 5 in. w.g. Natural Gas, 11 in. w.g. LPG/Propane
1