Page 45
First and second stage cooling operate independent of
each other and can modulate back and forth according to
the thermostat demand.
First Stage Cooling (Low Capacity)
1 - Cooling demand initiates at Y1 at the thermostat.
2 - Voltage from terminal Y passes through S4
high pressure switch, energizes K1 compressor
contactor, passes through the low pressure switch
(S87) and returns to common side of the 24VAC
power.
3 - K1 closes, energizing B1 compressor and B4
outdoor fan.
4 - Solenoid L34 is not energized so the slider ring
remains open, limiting compressor to low capacity.
Second Stage Cooling (High Capacity)
Compressor is operating in rst stage cooling. Second
stage thermostat demand sends voltage to rectier plug
D4. D4 converts the AC voltage to DC voltage and ener-
gizes L34 unloader solenoid. L34 closes the slider ring,
allowing the compressor to operate at high capacity.