FAHRENHEIT DEGREES TEMPERATURE SETTING
In order to set the measurement unit from Celsius degrees to Fahrenheit
degrees and vice versa, enter the conguration mode by holding down the
keys and “until the display shows Con”, then hold down the
two keys and for a few seconds, until the display returns to
the usual screen.
Switching from Celsius to Fahrenheit or vice versa also forces a
reset of the installer conguration to default values.
0. 0
P12
Room temperature
offset (°F)
12. 0..12. 0
50
P13
Heating set-point
lower limit (°F)
41 ..95 
86
P14
Heating set-point
upper limit (°F)
41 ..9 5    
50
P15
Cooling set-point
lower limit (°F)
41 ..95 
86
P16
Cooling set-point
upper limit (°F)
41 ..95 
32
P17
Anti-freeze threshold
temperature (°F)
32 .. 6 0
0
P18
Economy
reduction (°F)
0 ..18
0. 4
P19
Room temperature
hysteresis (°F)
0. 4 ..1. 8
5. 0
P20
Neutral zone
width (°F)
0. 0 ..20. 0
0
P21
Fan delay at
turn-on (seconds)
0 ..600
0
P22
Fan delay at
turn-off (seconds)
0 ..600
104
P23
Heating delivery
temperature threshold (°F)
32 ..210
59
P24
Cooling delivery
temperature threshold (°F)
32 ..210
0
P25
Dirty lter warning
time (x 100 hours)
0 .. 5 0
-