Table 2: Extended conguration parameters (to set temperatures to Fahrenheit degrees see appendix A page 130).
DFLT PAR. DESCRIPTION SET VALUES
17 C01
Changeover
lower threshold (°C)
0 .. 2 4
30 C02
Changeover
upper threshold (°C)
26 .. 4 8
2. 0
C03
Heating proportional band
(°C)
0. 8 .. 8 . 0
2. 0
C04
Cooling proportional band
(°C)
0. 8 .. 8 . 0
0
C05
Heating integrating
time (minutes)
0 .. 6 0
0
C06
Cooling integrating
time (minutes)
0 .. 6 0
20
C07
Heating valve minimum
power (%)
0 .. 5 0
0
C08
Cooling valve minimum
power (%)
0 .. 5 0
3
C09
Fan motor speeds number
1 .. 3
0
C10
Fan speed “ “
button limitation
0 .. 1 5
33
C11
Minimum fan power (%)
1 .. 100
66
C12
Medium fan power (%)
1 .. 100
100
C13
Maximum fan power (%)
1 .. 100
50 C14
Minimum fan power with
electric heater ON
0 .. 100
0 C15
Fan signal lower limit
0 .. 1 0 .0
100 C16
Fan signal upper limit
0 .. 1 0 .0
1 C17
Terminal 3 input function
0 .. 2 0
3 C18
Terminal 4 input function
0 .. 2 0
9 C19
Terminal 16 input function
0 .. 2 1
0 C20
On/Off “ “
button limitation
0 .. 7
1.5 C21
∆ integration set point (°C)
0. 0 .. 2 0 . 0
0 C22
Default display
0
Room
Temperature
1
Set point
Temperature
0 C23
Terminal 8 output function
0 .. 2
Tab. 4
Tab. 3
Tab. 4
Tab. 4
Tab. 5
Tab. 6