Page 15
TABLE 3 
OUTDOOR TERMINATION USAGE*
Input Size
Vent Pipe 
Dia. in.
STANDARD CONCENTRIC
Flush 
Mount Kit
Wall Kit
Wall Ring 
Kit
Field 
Fabricated
1-1.2 inch 2 inch 3 inch
2 inch 3 inch 2 inch
71M80 
(US) 
4
44W92 
(CA)
69M29 
(US) 
4
44W92 
(CA)
60L46 (US) 
4
44W93 (CA)
51W11 
(US) 
51W12 
(CA)
22G44 
(US) 
4
30G28 
(CA)
44J40 
(US) 
4
81J20 
(CA)
15F74
045
2
3
YES YES
1
YES
1
YES
5
YES
2
YES
2-1/2
3
YES YES
1
YES
1
YES
5
YES
2
YES
3
3
YES YES
1
YES
1
YES
5
YES
2
YES
070
2
3
YES YES
1
YES
1
YES
5
YES
2
YES
2-1/2
3
YES YES
1
YES
1
YES
5
YES
2
YES
3
3
YES YES
1
YES
1
YES
5
YES
2
YES
090
2
3
YES YES YES
5
YES YES YES
2-1/2
3
YES YES YES
5
YES YES YES
3
3
YES YES YES
5
YES YES YES
110
2 YES YES YES
5
YES YES YES
2-1/2 YES YES
5
YES YES YES
3 YES YES
5
YES YES YES
NOTE - Standard Terminations do not include any vent pipe or elbows external to the structure. Any vent pipe or elbows external to the structure must be included in total 
vent length calculations. See vent length tables.
* Kits must be properly installed according to kit instructions.
1Requires eld-provided outdoor 1-1/2” exhaust accelerator.
2Concentric kits 71M80 and 44W92 include 1-1/2” outdoor accelerator, when used with 045 and 070 input models.
3 Flush mount kits 51W11 and 51W12 includes 1-1/2 in. outdoor exhaust accelerator, required when used with 045, 070 and 090 input models.
4 Termination kits 30G28, 44W92, 44W93 and 81J20 are certied to ULC S636 for use in Canada only.
5 See table 8 for vent accelerator requirements.
Joint Cementing Procedure
All cementing of joints should be done according to the 
specications outlined in ASTM D 2855.
 DANGER
DANGER OF EXPLOSION!
Fumes from PVC glue may ignite during system check. 
Allow fumes to dissipate for at least 5 minutes before 
placing unit into operation..
1 -   Measure and cut vent pipe to desired length.
2 -  Debur and chamfer end of pipe, removing any ridges 
or rough edges. If end is not chamfered, edge of pipe 
may remove cement from tting socket and result in 
a leaking joint.
NOTE - Check the inside of vent pipe thoroughly for 
any obstruction that may alter furnace operation.
3 - Clean and dry surfaces to be joined.
4 -  Test  t joint  and mark depth  of tting on outside of 
pipe.
5 -  Uniformly apply a liberal coat of PVC primer for PVC 
or use a clean dry cloth for ABS to clean inside socket 
surface  of  tting  and  male  end  of  pipe  to  depth  of 
tting socket.
NOTE - Time is  critical at this  stage. Do  not allow 
primer to dry before applying cement.
6 -  Promptly apply solvent cement to end of pipe and 
inside  socket  surface  of  tting.  Cement  should  be 
applied lightly but uniformly to inside of socket. Take 
care to keep excess cement out of socket. Apply 
second coat to end of pipe.
7 -  Immediately after applying last coat of cement to 
pipe, and while both inside socket surface and end 
of pipe  are wet with cement, forcefully insert end of 
pipe into socket until it bottoms out. Turn PVC pipe 
1/4 turn during assembly (but not after pipe is fully 
inserted) to distribute cement evenly. DO NOT turn 
ABS or cellular core pipe.
NOTE - Assembly  should  be  completed  within  20 
seconds  after  last  application  of  cement.  Hammer 
blows should not be used when inserting pipe.