EasyManua.ls Logo

Lennox MLA012S4S-1P - Page 123

Lennox MLA012S4S-1P
168 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
123
Error Code: P4
Description: Hightemperaturesensedatcompressordischargeline.
General Note: Whenthecompressordischargetemperature(T5)ismorethan239°F(115°C)for10seconds,thecompressorwillstopand
restarttillT5islessthan194°F(90°C).
Temperatureprotectionofcompressor.
Checkwhetherthecompressordischargetemp.is
morethan239°F(115°C)?
No
Checkwhethertheconnectionisrightbetweencom-
pressordischargetemp.sensorandPCBaccordingto
wiringdiagrams?
Checkwhetherthe
refrigerantisleak.
Yes
Stopleakingandadd
refrigerant.
Yes
No
Correctthewiringconnection.
No
Yes
Measuretheresistancevalueofcompressordis-
chargetemp.sensor.Ifthevalueisnotnormalis
normalrefertotheAppendix2?
Replacethecompressor
dischargetemp.sensor.
No
Yes
ReplaceoutdoormainPCB.
No
Replacehighpressurevalveassy.

Table of Contents

Other manuals for Lennox MLA012S4S-1P

Related product manuals