EasyManua.ls Logo

Lennox MPA018S4M-*P

Lennox MPA018S4M-*P
168 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
166
31.7. Electronic Expansion Valve (EXV) Control
a. EXVwillbefullyclosedwhenturningonthepower.ThenEXVwillbestandbywith350Popenandwillopentotarget
angle after compressor starts.
b. EXVwillclosewith-160Pwhencompressorstops.ThenEXVwillbestandbywith350Popenandwillopentotarget
angle after compressor starts.
c. TheactionpriorityoftheEXVsisA-B-C-D.
d. CompressorandoutdoorfanstartoperationonlyafterEXVisinitialized.
31.7.1. Cooling mode
TheinitialopenangleofEXVis250P,adjustmentrangeis100-350p.Whentheunitstarttoworkfor3minutes,theoutdoor
willreceiveindoorunits(ofcapacitydemand)T2Binformationandcalculatetheaverageofthem.Aftercomparingeach
indoor’sT2Bwiththeaverage,theoutdoorgivesthefollowingmodicationcommands:IftheT2B>average,therelevant
valveneedsmore16popen;IftheT2B=average,therelevantvalve’sopenrangeremains;IftheT2B<average,therelevant
valve needs more 16p close.
Thismodicationwillbecarriedoutevery2minutes.
31.7.2. Heating mode
The initial open angle of EXV is 250P, adjustment range is 100-350p. When the unit start to work for 3 minutes, the
outdoorwillreceiveindoorunits(ofcapacitydemand)T2informationandcalculatFrom SubjectReceived Size
Categories
After comparing each indoor’s T2 with the average, the outdoor gives the following modication commands: If the
T2>average+2,therelevantvalveneedsmore16pclose;
Ifaverage+2≥theT2≥average-2,therelevantvalve’sopenrangeremains;
IftheT2<average-2,therelevantvalveneedsmore16popen.
Thismodicationwillbecarryoutevery2minutes.

Table of Contents

Other manuals for Lennox MPA018S4M-*P

Related product manuals