EasyManua.ls Logo

Lennox MPA018S4M-*P

Lennox MPA018S4M-*P
168 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
91
19.3. Outdoor Unit Spot Check Function
ThereisacheckswitchinoutdoorPCB.PushtheswitchSW1tocheckthestatesofunitwhentheunitisrunning.Thedigital
displaytubewilldisplaythefollowprocedurewhenpushSW1eachtime.
SW1
Figure 63. SW1 Location
Table 3. Status Indicators
Display Remark
0 NormalDisplay Displayrunningfrequency,runningstateormalfunctioncode
1 Quantityofindoorunitsingoodconnection
Actual data
Display Number of indoor units
1 one
2 two
3 three
4 four
5 ve
2 Outdoorunitrunningmode Off:0,Fanonly:1,Cooling:2,Heating:3,Forcedcooling:4
3 Indoor unit A capacity
Thecapacityunitishorsepower.Iftheindoorunitisnotconnected,thedigitaldisplay
tubewillshow:“――”
(9K:1HP,12K:1.2HP,18K:1.5HP)
4 IndoorunitBcapacity
5 Indoor unit C capacity
6 IndoorunitDcapacity
7 Indoor unit E capacity

Table of Contents

Other manuals for Lennox MPA018S4M-*P

Related product manuals