Menu Interface SETTINGS (Continued)
SETTINGS > SETPOINTS
DAMPER
Use SETTINGS > SETPOINTS > DAMPER as shown in
the following diagram; default settings will be used. You
may adjust those settings to suit the building’s require-
ments. The following diagram shows the DAMPER menu’s
structure and how to make changes.
OAS TEMP STPT
ECONOMIZER MODE
TEMP MODE Set DIP sw1 to TMP −>
CONTROL
OAT STPT 41−70ºF 60ºF
OFFSET 0−40ºF 15ºF. . . . . . . . .
ENTH MODE Set DIP sw1 to ODE −>
GLOBAL MODE Set DIP sw1 to GLO −>
SUPPLY AIR STPT 55ºF
MIN OCP BLOWER LOW 15%
MIN OCP BLOWER HIGH MIN POS SET POT
FAH DISABLED
FAC DISABLED
Use arrows to move
DAMPER
SEE
FIGURE 6
(PAGE 19)
NOTE: FOR
DETAILS, SEE
ECONOMIZER
SECTION Page 18
SETPOINTS
SETTINGS > CONTROL
In the SETTINGS menu, use until CONTROL is dis-
played. Press to enter the CONTROL menu.
View the current system setpoints setup in the M2 unit con-
troller.
Use arrows to move
GUIDED SETUP
LOCAL
THERMOSTAT
L CONN
BACNET
LONTALK
MSAV
REHEAT
CONTROL
SETTINGS > CONTROL
LOCAL
Select SETTINGS > CONTROL > LOCAL as shown in the
following diagram; default settings will be used. You may
adjust those settings to suit the building’s requirements.
LOCAL
RETURN AIR BACKUP YES/NO
OCP HEAT BU STPT XX.XºF
UNOCP HEAT BU STPT XX.XºF
OCP COOL BU STPT XX.XºF
UNOCP COOL BU STPT XX.XºF
CONTROL
SETTINGS > CONTROL
THERMOSTAT SETUP
No setting changes are required. Simply hook up to Smart-
Wiret connections.
SETTINGS > CONTROL
CONTROL: L CONN (L Connection)
Select SETTINGS > CONTROL > L CONN as shown in
the following diagram; default settings will be used. You
may adjust those settings to suit the building’s require-
ments.
L CONN
ADDR:XX
CONTROL MODE
BACKUP MODE (1,2,3)
OCP HEAT BU STPT XX.XºF
UNOCP HEAT BU STPT XX.XºF
OCP COOL BU STPT XX.XºF
UNOCP COOL BU STPT XX.XºF
STARTUP DELAY (2 − 30) 2 MIN
OVERRIDE TIMER (0 8HR) 1 HR
BLOWER ON OCP
NETWORK COMFORT SENSOR
CONTROL
0. NONE
1. TSTAT
2. RAT
3. ZAT
CYCLES OR
CONTINUOUS