Page 9
Menu Interface DATA
From the DISPLAY mode, press and then use to
scroll to DATA. Next, press
to enter the DATA menu.
Use until desired item is displayed.
Use DATA to view information stored in the M2 Unit Con-
troller.
DATA
RUN TIMES
HISTORY
SENSORS
NETWORK
FACTORY
Use arrows to move
DATA > RUNTIMES
In the DATA menu, use until RUNTIMES is displayed.
Press to enter the RUNTIMES menu.
View accumulated runtime hours logged against various
components and systems by the M2 unit controller.
Use arrows to move
POWER ON
FILTER: XX HRS
BELT: XX HRS
UV LAMP: XX HRS
BLOWER: XX HRS
COOLING
HEATING
FREE COOLING: XX HRS − XX CYC
FANS
EXHAUST
REHEAT: XX HRS − XX CYC
RUNTIMES
As each entry is listed, its ac-
cumulated runtime is automati-
cally displayed.
DATA > HISTORY
In the DATA menu, use until HISTORY is displayed.
Press to enter the HISTORY menu.
Read the accumulated historical data of alarms, status,
and USB reports logged by the M2 unit controller.
Use arrows to move
ALARMS
STATUS
LAST USB REPORT
READ INSTALL
CLEAR HISTORY
HISTORY
Use the up/down arrows
to scroll through a list of
ALARMS and STATUS
events
DATA > SENSORS
In the DATA menu, use until SENSORS is displayed.
Press to enter the SENSORS menu.
View the current sensed value for various systems being
sent to the M2 unit controller.
TSTAT
BRPM:XX
DPOS:XX%
OAT:XXºF
RAT:XXºF
DAT:XXºF
ZAT:XXºF
IAQ: XX PPM
SMK: OFF/ON
RH: XX%
IE: XX MA
OE: XX MA
GLO: OFF/ON
DI2: OFF/ON
DI3 OFF/ON
DI4: OFF/ON
Use arrows to move
SENSORS
As each sensor is listed, its
reading is automatically dis-
played.