IOM / Rooftop Smart and Linéa Range - Page 85
This option is used for making a connection to the BMS
only, by a set of volt free contacts.
It requires the addition of a KP05 card, if this is not already
in place, and a KP12 card.
Input connection must be by screened cable only.
Limits of relays :
10A 250V with resistive load
4A 250V with inductive load.
Input Function
A Instruction shift :
A 0/20mA signal can be used to add a linear
shift of 0 to 10 °C to the setpoint temperature
(mid-point between air-conditioning and
heating setpoint). If your command signal is
a different type, our engineers can advise you
on the type of interface to use before input to
the CLIMATIC (0-10V with interface)
B Unit on/off (ROOF-TOP on when unit is off).
C Contact - force night operation
D Contact - force day operation
E Contact - force operation at 50%.
F Lock heating function
G Lock air-conditioning function.
H Feedback of information from an external
client component
BMS VOLBMS VOL
BMS VOLBMS VOL
BMS VOL
T FREE CONTT FREE CONT
T FREE CONTT FREE CONT
T FREE CONT
ACTS KITACTS KIT
ACTS KITACTS KIT
ACTS KIT
12V 12V
J3
KP 12.2
200mA
1 2 3 4 5 6 7 8
J2
J3
J6
J4
RL1 RL2 RL3 RL4 RL5 RL6 RL7 RL8
Com No Com No Com No Com No Com NoCom No Com No Com No
J3 J1
+18V
+18V
KP05
8 7 2 1
B
C
DF
E
A
GH
a
b
cd e f g
Output Function
a Signal filter fault
b Signal fan fault
c Signal compressor fault
d Signal fault on gas burner or electric coil.
e Signal supplying temperature greater than
setpoint (Setpoint 74)
f Signal supplying temperature less than
setpoint (setpoint 71)
g Command from an external client component
Figure 77