IOM / Rooftop Smart and Linéa™ Range - Page 87
DESCRIPTION OF PARAMETERS
Parameters are defined for the time slot. Select by instruction 08 setting.
0 = DAY / 1 = WEEKEND / 2 = NIGHT / 3 = unused / 4 = MORNING / 5 =MIDDAY / 6 = EVENING / 7 = BMS.
Instruction Description
09 Day of the week of start of setting . From 1 to 7, 1 = Sunday.
10 Hour of start of setting
11 Minutes for start of setting
12 Day of the end of setting
13 Hour of end of setting
14 Minutes of end of setting
15 Setpoint in heating
16 Setpoint in air conditioning
23 Fan operation in regulation zone *. ON on OFF off
24 Fan operation in neutral zone*. ON on OFF off
25 Automatic fan operation in neutral zone*. In this zone after operation in air-conditioning mode, the fan is off. If
after one hour the ambient air is still in this zone the fan is started up again.
29 Low noise
30 Instruction used to force operation in the current setting
CLIMACLIMA
CLIMACLIMA
CLIMA
TIC™ PTIC™ P
TIC™ PTIC™ P
TIC™ P
ARAR
ARAR
AR
AMETERSAMETERS
AMETERSAMETERS
AMETERS
* The regulation zone is defined for a temperature less than
the heating instruction or greater than the air-conditioning
instruction. The neutral zone is between these 2 values.
NOTE: The end of the night slot night is defined by the start
of the morning slot : this is why there is no need to define
the end of the night slot in the table below
Setpoint
value DAY WEEK-END NIGHT MORNING MIDDAY EVENING BMS
for KP02 = 0 = 1 = 2 = 4 = 5 = 6 = 7
9 -7-----
10 - 22 22 6 12 19 -
11 -00000-
12 -2-----
13 -6-61219
14 -0-000
15 23.0 30.0 30.0 23.0 23.0 23.0 23.0
16 19.0 10.0 10.0 19.0 19.0 19.0 19.0
17 Off Off Off Off Off Off Off
18 0000000
19 100 100 100 100 100 100 100
20 0.0 0.0 0.0 0.0 0.0 0.0 0.0
21 30.0 30.0 30.0 30.0 30.0 30.0 30.0
22 20 0 0 0 20 20 20
23 On On On On On On On
24 On Off Off Off On On On
25 Off Off Off Off Off Off Off
26 Off Off Off Off Off Off Off
27 Off Off Off Off Off Off Off
28 Off Off Off Off Off Off Off
29 Off Off Off Off Off Off Off
30 Off Off Off Off Off Off Off