Page 34
 of the circuit being connected to one of the provided 
neutral terminals. See FIGURE 55 for location of 
terminal. This terminal is energized when the indoor 
blower is operating.
8 -   One line voltage “HUM” 1/4” spade terminal is 
provided on the furnace integrated control. Any 
humidier or other 120V accessory rated up to one 
amp can be connected to this terminal with the 
neutral leg of the circuit being connected to one of 
the provided neutral terminals. See FIGURE 55 for 
location of terminal. This terminal is energized in the 
heating mode when the indoor blower is operating.
9 -   One 24V “H” terminal is provided on the furnace 
integrated  control  terminal  block.  Any  humidier 
rated up to 0.5 amp can be connected to this 
terminal with the ground leg of the circuit being 
connected to either ground or the “C” terminal. See 
FIGURE 55 for location of terminal.
10 - 1 Install the room thermostat according to the 
instructions provided with the thermostat. See 
TABLE 15 for thermostat connections. If the 
furnace is being matched with a heat pump, refer 
to the instruction packaged with the dual fuel 
thermostat.
NOTE - The discharge air temperature sensor is intended 
to be mounted downstream of the heat exchanger and air 
conditioning coil. It must be placed in free airow, where 
other accessories (humidiers, UV lights etc.) will not in-
terfere with its accuracy. Wiring distance between the fur-
nace  and  discharge  air  sensor  should not  exceed 10 ft. 
when wired with 18-gauge thermostat wire.
TABLE 13 
Run Length - Non Communicating
Wire Run Length AWG# Insulation / Core Types
Less thsn 100’ 
(30m)
18
Color-coded, temperature 
rating 95ºF (35ºC) 
minimum, solid core. 
(Class II 16 Rated 
Wiring)
More than 100’ 
(30m)
16
TABLE 14 
Run Length - Non Communicating
Wire Run Length AWG# Insulation / Core Types
Maximum length 
of wiring for all 
connections on the 
RSBus is limited 
to 1500 feet (457 
meters).
18
Color-coded, temperature 
rating 95ºF (35ºC) 
minimum, solid core. 
(Class II 16 Rated 
Wiring)
Thermostat Selection
The SLP99UHV is designed to operate in a variable rate 
capacity mode using a two-stage thermostat. The SL-
P99UHV  will  automatically  adjust  ring  rate  based  upon 
thermostat cycle times.
A communicating thermostat must be used in communi-
cating applications. Refer to the instructions provided with 
the thermostat for installation, set-up and operation.
For optimal performance in non-communicating applica-
tions, Lennox recommends use of a ComfortSense® 7500 
high quality electronic digital thermostat or any other with 
adjustable settings for 1st stage / 2nd stage on / o dier-
entials and adjustable stage timers.
Lennox recommends the following two-stage thermostat 
set-up for optimal variable rate capacity mode: First heat 
stage  dierential  set  to  1/2  to  1  degree  F;  second  heat 
stage  dierential  set  to  1/2  or  1  degree  F;  second  heat 
stage upstage timer disabled, or set to maximum (1 hr 
minimum).
Indoor Blower Speeds
NOTE - When the SLP99UHV is used with a communicat-
ing  thermostat, proper indoor blower speed selections are 
made by the thermostat.
1 -   When the thermostat is set to “FAN ON,” the indoor 
blower will run continuously at a percentage of 
the second- stage cooling speed when there is no 
cooling or heating demand. The percentage is set 
using DIP switches 6 and 7. See TABLE 25 on page 
48 for allowable circulatuion speeds.
2 -   When the SLP99UHV is running in the heating 
mode, the integrated control will automatically 
adjust the blower speed to match the furnace ring 
rate. This speed can be adjusted up or down by 
7.5% or 15% using DIP switches 14 through 16 
for the low heat speed and 17 through 19 for the 
high heat speed. See TABLE 24 on page 48 for 
allowable heating speeds.
3 -   When there is a cooling demand, the indoor blower 
will run on the cooling speed designated by the 
positions of DIP switches 8 through 11.
Generator Use - Voltage Requirements
The following requirements must be kept in mind when 
specifying a generator for use with this equipment:
•   The furnace requires 120 volts + 10% (Range: 108 volts 
to 132 volts).
•   The furnace operates at 60 Hz + 5% (Range: 57 Hz to 
63 Hz).
•   The furnace integrated control requires both polarity 
and proper ground. Both polarity and proper grounding 
should be checked before attempting to operate the fur-
nace on either permanent or temporary power.
•   Generator should have a wave form distortion of less 
than 5% THD (total harmonic distortion).