Page 10
NOTE - When the furnace is installed on a platform in a 
crawlspace,  it  must  be  elevated  enough  to  avoid  water 
damage and to allow the evaporator coil to drain.
HORIZONTAL SUSPENSION KIT
Bracket
(typical)
Metal Strap
(typical)
Air
Flow
Internal Brace
(provided with kit)
FIGURE 12 
Platform Installation of Horizontal Unit
1 -   Select location for unit keeping in mind service and 
other necessary clearances. See FIGURE 11.
2 -   Construct a raised wooden frame and cover frame 
with a plywood sheet. If unit is installed above 
nished  space,  fabricate  an  auxiliary  drain  pan 
to be installed under unit. Set unit in drain pan as 
shown in FIGURE 13. Leave 8 inches for service 
clearance below unit for condensate trap.
3 -   Provide a service platform in front of unit. When 
installing the unit in a crawl space, a proper support 
platform may be created using cement blocks.
4 -    Route auxiliary drain line so that water draining from 
this outlet will be easily noticed by the homeowner.
5 -   If necessary, run the condensate line into a 
condensate pump to meet drain line slope 
requirements. The pump must be rated for use 
with condensing furnaces. Protect the condensate 
discharge line from the pump to the outside to avoid 
freezing.
6 -     Continue with exhaust, condensate and intake 
piping installation according to instructions.
*Gas connector may be
used  for  Canadian
able  by  local  authority
having jurisdiction.
*GAS CONNECTION
RAISED
PLATFORM
SERVICE PLATFORM
INTAKE PIPE
EXHAUST PIPE
FIGURE 13 
Return Air -- Horizontal Applications
Return air must be brought in through the end of a fur-
nace  installed  in  the  horizontal  position.  The  furnace  is 
equipped with a removable bottom panel to facilitate in-
stallation. See FIGURE 7.
Filters
This unit is not equipped with a lter or rack. A eld-provid-
ed lter is required for the unit to operate properly. TABLE 
1 lists recommended lter sizes.
 IMPORTANT
If a higheciency lter is being installed as part of this 
system to ensure better indoor air quality, the lter must 
be  properly  sized.  Higheciency  lters  have  a  higher 
static pressure drop than standard eciency glass/foam 
lters. If the pressure drop is too great, system capacity 
and performance may be reduced. The pressure drop 
may also cause the limit to trip more frequently during 
the winter and the indoor coil to freeze in the summer, 
resulting in an increase in the number of service calls.
Before  using  any  lter  with  this  system,  check  the 
specications provided by the lter manufacturer against 
the data given in the appropriate Lennox Product 
Specications bulletin. Additional information is provided 
in Service and Application Note ACC002 (August 2000).
A lter must be in place when the unit is operating.
NOTE - In upow applications where side return air lter is 
installed on same side as the condensate trap, make sure 
that  clearance  is  maintained  to  ensure  future  access  to 
the lter access panel.
TABLE 1
Furnace 
Cabinet Width
Filter Size
Side Return Bottom Return
17-1/2” 16 X 25 X 1 (1) 16 X 25 X 1 (1)
21” 16 X 25 X 1 (1) 20 X 25 X 1 (1)
24-1/2” 16 X 25 X 1 (2) 24 X 25 X 1 (1)
Duct System
Use  industry-approved  standards  to  size  and  install  the 
supply and return air duct system. This will result in a qui-
et and low-static system that has uniform air distribution. 
See below for proper duct installation.
FIGURE 14 
HORIZONTAL UNIT
SUPPLY
AIR
SUPPLY
AIR
Install self tapping screws
to seal any potential air
leaks
UPFLOW UNIT