Page 56
6 -   If the heating demand continues beyond the third-
stage on delay, the integrated control energizes the 
inducer at high speed. The indoor blower motor is 
adjusted to a speed which is appropriate for the 
target rate.
7 -   When  the thermostat  heating  demand is  satised, 
the gas valve is de-energized and the combustion 
air inducer begins a 20-second post-purge. The 
eld-selected indoor blower o delay begins.
8 -   When the combustion air post-purge period is 
complete, the inducer is de-energized. The indoor 
blower is de-energized at the end of the o delay.
Service
 WARNING
ELECTRICAL SHOCK, FIRE,
OR EXPLOSION HAZARD.
Failure to follow safety warnings exactly could result in 
dangerous operation, serious injury, death or property 
damage.
Improper servicing could result in dangerous operation, 
serious injury, death, or property damage.
Before servicing, disconnect all electrical power to 
furnace.
When servicing controls, label all wires prior to 
disconnecting.
Take care to reconnect wires correctly.
Verify proper operation after servicing.
 WARNING
The blower access panel must be securely in place when 
the blower and burners are operating. Gas fumes, which 
could contain carbon monoxide, can be drawn into living 
space resulting in personal injury or death.
Annual Furnace Maintenance
At the beginning of each heating season, and to comply 
with the Lennox Limited Warranty, your system should be 
checked as follows:
1 -   Check wiring for loose connections, voltage at 
indoor unit and amperage of indoor motor.
2 -   Check the condition of the belt and shaft bearings 
if applicable.
3 -  Inspect all gas pipe and connections for leaks.
4 -   Check  the  cleanliness  of  lters  and  change  if 
necessary (monthly).
5 -   Check the condition and cleanliness of burners and 
heat exchanger and clean if necessary.
6 -    Check the cleanliness of blower assembly and 
clean the housing, blower wheel and blower motor 
if necessary.
7 -   Inspect the condensate drain and trap for leaks and 
cracks. The drain and trap must also be cleaned 
and the trap must be primed with water. Inspect the 
rubber hoses connected to the pressure switches for 
cracks or loose connections, replace as necessary. 
Remove the rubber hoses from the cold end header 
box and inspect for any blockage, clean as needed. 
If strainers are installed in the hoses remember to 
remove and clean before reinstalling the hoses.
8 -   Evaluate the heat exchanger integrity by inspecting 
the heat exchanger per the AHRI heat exchanger 
inspection procedure. This procedure can be 
viewed at www.ahrinet.org
9 -   Ensure sucient combustion air is available to the 
furnace. Fresh air grilles and louvers (on the unit 
and in the room where the furnace is installed) 
must be properly sized, open and unobstructed to 
provide combustion air.
10 -  On condensing furnaces, inspect the furnace intake 
and exhaust pipes to make sure they are in place, 
structurally sound, without holes, blockage or 
leakage and the exhaust pipe is sloped toward the 
furnace. Inspect terminations to ensure they are free 
of obstructions and are structurally sound. Inspect 
the furnace return air duct connection to ensure the 
duct is sealed to the furnace. Check for air leaks on 
supply and return ducts and seal where necessary.
11 -  Inspect the furnace return air duct connection to 
ensure the duct is sealed to the furnace. Check for 
air leaks on supply and return ducts and seal where 
necessary.
12 -  Check the condition of the furnace cabinet insulation 
and repair if necessary.
13 -   Perform a complete combustion analysis during the 
furnace inspection to ensure proper combustion 
and operation. Consult Service Literature for proper 
combustion values.
14 -  Verify operation of CO detectors and replace 
batteries as required.
Perform a general system test. Turn on the furnace to 
check operating functions such as the start-up and shut-
o operation.
1 -   Check the operation of the ignition system, inspect 
and  clean  ame  sensor.  Check  microamps  before 
and after. Check controls and safety devices (gas 
valve,  ame  sensor,  temperature  limits).  Consult 
Service Manual for proper operating range. Thermal 
Limits should be checked by restricting airow and 
not disconnecting the indoor blower. For additional 
details, please see Service and Application Note 
H049.