EasyManuals Logo

Lennox SL280UHV series Unit Information

Lennox SL280UHV series
78 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #49 background imageLoading...
Page #49 background image
Page 49
The gas valve is factory set and should not require adjust-
ment. All gas valves are factory regulated.
Manifold Adjustment Procedure:
1 - Connect test gauge to manifold pressure tap
(FIGURE 19 and FIGURE 20) on gas valve.
2 - Ignite unit on low re and let run for 5 minutes to
allow for steady state conditions.
3 - After allowing unit to stabilize for 5 minutes, record
manifold pressure and compare to value given in
TABLE 19.
4 - If necessary, make adjustments. FIGURE 19 and
FIGURE 20 show location of high re and low re
adjustment screw.
5 - Repeat steps 2, 3 and 4 on high re.
6 - Shut unit o󰀨 and remove manometer as soon as an
accurate reading has been obtained. Take care to
replace pressure tap plug.
7 - Start unit and perform leak check. Seal leaks if
found.
F- Proper Gas Flow (Approximate)
Furnace should operate at least 5 minutes before check-
ing gas ow. Determine time in seconds for two revolu-
tions of gas through the meter. (Two revolutions assures
a more accurate time.) Divide by two and compare to time
in TABLE 17. If manifold pressure matches TABLE 19 and
rate is incorrect, check gas orices for proper size and
restriction.
NOTE- To obtain accurate reading, shut o all other gas
appliances connected to meter.
G- Proper Combustion
Furnace should operate minimum 15 minutes with correct
manifold pressure and gas ow rate before checking com-
bustion. See sections E- and F-. Take combustion sam-
ple beyond the ue outlet and compare to TABLE 18. The
maximum carbon monoxide reading should not exceed
100 ppm
TABLE 17
GAS METERING CLOCKING CHART
SL280
Unit
Natural 1000 btu/
cu ft
LP 2500 btu cu/cu ft
Seconds For One Revolution
1 cu ft
dial
2 cu fr
dial
1 cu ft
Dial
2 cu ft
Dial
-045 80 160 200 400
-070 55 110 136 272
-090 41 82 102 204
-110 33 66 82 164
-135 27 54 68 136
IMPORTANT
For safety, shut unit o󰀨 and remove manometer as
soon as an accurate reading has been obtained.
Take care to replace pressure tap plug.
TABLE 18
Firing Rate CO2% For Nat CO2% For L.P.
High Fire 6.8 - 7.4 7.5 - 9.0
Low Fire 4.2 - 5.7 5.0 - 6.0
The carbon monoxide reading should not exceed 100 ppm.
H- High Altitude
The manifold pressure, gas orice and pressure switch
may require adjustment or replacement to ensure proper
operation at higher altitudes. See TABLE 19 for manifold
pressures and TABLE 20, TABLE 21 and TABLE 22for
pressure switch and gas conversion kits.

Other manuals for Lennox SL280UHV series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox SL280UHV series and is the answer not in the manual?

Lennox SL280UHV series Specifications

General IconGeneral
BrandLennox
ModelSL280UHV series
CategoryFurnace
LanguageEnglish

Related product manuals