6/2013 507163-01
*2P62013* *P507163-01*
Page 1
2013 Lennox Industries Inc.
Dallas, Texas, USA
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
These instructions are intended as a general guide and do
not supersede local codes in any way. Consult authorities
having jurisdiction before installation.
WARNING
Improper installation, adjustment, alteration, service or
maintenance can cause personal injury, loss of life, or
damage to property.
Installation and service must be performed by a licensed
professional installer (or equivalent) or a service agency.
IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of
refrigerant (CFCs, HCFCs and HFCs) as of July 1, 1992.
Approved methods of recovery, recycling or reclaiming
must be followed. Fines and/or incarceration may be
levied for noncompliance.
IMPORTANT
This unit must be matched with an indoor coil as speci
fied in Lennox SSB*H4 Product Specification bulletin.
Coils previously charged with HCFC-22 must be
flushed.
NOTICE TO INSTALLER
UNIT PLACEMENT
It is critical for proper unit operation to place outdoor unit on an
elevated surface as described in Unit Placement section on page 7.
BRAZING LINE SET TO SERVICE VALVES
It is imperative to follow the brazing technique illustrated starting on
page 12 to avoid damaging the service valve's internal seals.
INSTALLATION
INSTRUCTIONS
S-CLASS SSB*H4 Units
AIR CONDITIONER UNITS
507163-01
6/2013
Supersedes 506641-01
TABLE OF CONTENTS
Shipping and Packing List 1......................
General 1......................................
Unit Dimensions 2...............................
Model Number Identification 2....................
Unit Parts Arrangement 3........................
Operating Gauge Set and Service Valves 4.........
Recovering Refrigerant from Existing System 6.....
New Unit Placement 7...........................
Removing and Installing Panels 9.................
New or Replacement Line Set 10...................
Brazing Connections 12...........................
Flushing Line Set and Indoor Coil 15................
Installing Indoor Metering Device 16................
Leak Test Line Set and Indoor Coil 17...............
Evacuating Line Set and Indoor Coil 18.............
Electrical 19.....................................
Servicing Units Delivered Void of Charge 21.........
Unit Start-Up 21.................................
System Refrigerant 22............................
System Operation 25.............................
Maintenance 26..................................
Checklists 27....................................
Shipping and Packing List
Check the unit for shipping damage and listed times below
are intact. If damaged, or if parts are missing, immediately
contact the last shipping carrier.
1 - Assembled outdoor unit.
General
Two-stage S-Class SSB*H4 outdoor units use
HFC-410A refrigerant. This unit must be installed with a
matching indoor coil and line set as outlined in the Product
Specification bulletin. S-Class SSB*H4 outdoor units
are designed for use in expansion valve systems (TXV)
only. They are not designed to be used with other
refrigerant flow control devices. The Product Specification
bulletin lists a TXV kit that must be ordered separately.
Litho U.S.A.
Question and Answer IconNeed help?

Do you have a question about the Lennox SSB036H4S4 and is the answer not in the manual?

Lennox SSB036H4S4 Specifications

General IconGeneral
BrandLennox
ModelSSB036H4S4
CategoryAir Conditioner
LanguageEnglish

Summary

General Safety Warnings

Improper Installation Hazards

Improper installation, adjustment, alteration, service or maintenance can cause personal injury, loss of life, or damage to property.

Refrigerant Venting Regulations

The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFCs, HCFCs and HFCs).

Refrigerant Recovery Procedures

Disconnect Power Supply

Procedure to disconnect all power to the existing outdoor unit.

Connect Manifold Gauge Set

Connecting a gauge set, recovery cylinder, and recovery machine.

Recover Refrigerant

Methods for recovering existing HCFC-22 refrigerant.

Unit Placement and Positioning

Refrigerant Line Set Installation

Brazing Connections Procedures

Brazing Safety Precautions

Covers warnings and cautions related to fire, explosion, and health hazards during brazing.

Brazing Material Recommendations

Specifies recommended silver alloy brazing rods for different metal combinations.

Brazing Procedure Overview

Instructions for connecting gauge sets and cooling braze joints.

Brazing Step-by-Step

Attach Manifold Gauge Set

Connecting the manifold gauge set for brazing with nitrogen flow.

Brazing Final Steps

Flow Nitrogen

Flowing nitrogen at 1-2 psig through the gauge set during brazing.

Braze Line Set

Procedure for brazing the line set to service valves, including cooling.

Flushing Line Set and Indoor Coil

Fixed Orifice Removal Procedure

Procedure for removing existing fixed orifice metering devices.

Expansion Valve Removal Procedure

Procedure for removing existing expansion valve metering devices.

Connect Equipment for Flushing

Setting up gauges and equipment for the flushing procedure.

Flush Line Set and Coil

Steps for flushing the line set and indoor coil with refrigerant.

Indoor Metering Device Installation

Indoor Expansion Valve Installation

Steps for installing the expansion valve metering device on the indoor coil.

Leak Testing Line Set and Indoor Coil

Refrigerant Handling and EPA Regulations

Information on EPA regulations and safe handling of refrigerants.

Connect Gauge Set for Leak Test

Connecting the manifold gauge set for leak testing.

Procedure to Test for Leaks

Steps to pressurize the system with nitrogen and check for leaks.

Evacuating Line Set and Indoor Coil

Connect Gauge Set for Evacuation

Connecting the manifold gauge set and vacuum pump for evacuation.

Evacuate System to Micron Level

Procedure to evacuate the system to specific micron levels.

Electrical Connections and Thermostat

Unit Start-Up Procedures

Pre-Start Checks

Checks for fan binding, wiring connections, and opening service valves.

Gauge Set Connections for Charging

Connecting gauge set for testing and charging refrigerant.

System Refrigerant Procedures

Checking Indoor Airflow and Metering

Field Operational and Performance Checklists