EasyManuals Logo

Lennox VRB Series User Manual

Lennox VRB Series
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #22 background imageLoading...
Page #22 background image
22
12 34 5
66
The seal on the unit refrigerant piping connec-
tions should remain in place until the last pos-
sible moment. This will prevent dust or water
from getting into the refrigerant piping before it
is connected.
Flow the pipework with dry (oxygen-free) nitro-
gen (2.9 psig or 3 CFH) during brazing to avoid
oxidation which may block the refrigerant piping.
Do not use ux when brazing copper-to-copper
piping. Use phosphor copper brazing ller alloy
(BCuP) which does not require ux. Flux has a
harmful e󰀨ect on refrigerant pipe.
Use a wet cloth to insulate the shut o󰀨 valve dur-
ing brazing.
Use dedicated gauges and hoses with R-410A
equipment.
Pressure Test
Follow the pressure test specications in Table 2
for proper pressure testing procedures.
Ensure the unit service valves are fully closed
and haven’t become loose during transportation.
Use oxygen-free nitrogen to pressure test to 650
psig and hold for 1 hour.
Evacuate System
Follow the Lennox pressure test specications
in table 1 and the triple evacuation process de-
scribed on this page to pressure test and evacu-
ate the system.
Use a vacuum pump capable of evacuating to
lower than 500 Microns (0.5 Torr).
Do not open any of the outdoor unit shut-o󰀨
valves (possible max 5 valves). The outdoor unit
does not need to be evacuated.
Evacuate the system to 500 Microns (0.5 Torr), or
below, for 4 hours.
1 - Refrigerant pipe
2 - Part to be brazed
3 - Reducer
4 - Isolation valve
5 - Pressure-regulating valve
6 - Oxygen-free nitrogen
Figure 21. Brazing Best Practices
Table 2. Pressure Test Specications
1 3 bar 44 psig minimum of 10 minutes
2 15 bar 220 psig minimum of 10 minutes
3 32 bar 470 psig minimum of 10 minutes
4 45 bar 500 psig 1 hour. Stress test to
prove the integrity of the
complete installation.
5 32 bar 470 psig 24 hours. Lower system
pressure test, after
conrmation No. 4 was
successfully completed.
Triple Evacuation Procedure
A Micron or Torr gauge must be used for this
procedure.
1. Discharge the oxygen-free nitrogen and evacuate
the system to a reading of 8000 Microns (8 Torr)
using all service valves.
2. Break the vacuum by allowing nitrogen into the
three inter-connecting pipework port connections
(low pressure gas pipe, high pressure gas pipe
and liquid line pipe) until a positive pressure is
achieved.
3. Evacuate the system to a reading of 5000
Microns (5 Torr).
4. Break the vacuum by allowing nitrogen into the
three inter-connecting pipework port connections
(low pressure gas pipe, high pressure gas pipe
and liquid line pipe) until a positive pressure is
achieved
5. Evacuate the system to a minimum reading of
500 Microns (0.5 Torr).
6. For a moisture free system, ensure the vacuum
is held without movement for a minimum of 4
hours.
7. If pressure loss is detected, carry out steps 2
through 6 until no pressure loss is observed.
IMPORTANT!
Use only oxygen-free nitrogen (OFN).

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox VRB Series and is the answer not in the manual?

Lennox VRB Series Specifications

General IconGeneral
BrandLennox
ModelVRB Series
CategoryHeating System
LanguageEnglish

Related product manuals