24
Error Code Description
F0
Communication error between the indoor unit and the wired controller (may aect other indoor units in
the system.
F1 Communication error between the indoor unit and the controller.
F2 Controller EEPROM error.
E1 Communication error between the indoor unit and the outdoor unit.
E2 T1 temperature sensor error.
E3 T2A temperature sensor error.
E4 T2B temperature sensor error.
E5 Outdoor unit error.
E6 Fan motor error.
E7 Indoor unit EEPROM error.
E8 Indoor unit DC motor error.
EE Condensate pump error.
Error Code Description
E1 Communication error between indoor and outdoor units
E2 Indoor ambient temperature sensor (T1) error
E3 Middle evaporator temperature sensor (T2) error
E4 Evaporator outlet temperature sensor (T2B) error
E6 DC fan motor error
E7 EEPROM error
EE Water level alarm error
E7 EEPROM error
E0 Mode conict error
Ed Outdoor units error
FE IDU doesn’t have address when it is rst turned on
Table 6. Fault Code Display on Indoor Unit Receiver
Table 7. Fault Code Display on Controller
Troubleshooting
The unit is equipped with a receiver that has a digital
display that provides an error code.
• Refer to the table below to view the error codes.
• The error code will replace the temperature setting
displayed on the receiver.
• If more than one error has occurred, the codes will
alternate so that all codes are shown.
1. Make note of the code (E1, EE, etc.), then reset the
display by pressing the ON/OFF button on the unit
controller.
2. Press the ON/OFF button a second time to reapply
power to unit.
3. If the code is still displayed, disconnect and restore
power at the unit disconnect switch or circuit breaker.
4. If the problem was temporary, the code will not reap-
pear.
5. If the error code reappears after power has been bro-
ken and restored at the disconnect switch or circuit
breaker, call VRF Technical Support 1-844-438-8731.