11 Diagnostics
11.2 Diagnosing with the »Engineer«
48
Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
11.2 Diagnosing with the »Engineer«
In the »Engineer« under the Diagnostics tab, you will find INTERBUS diagnostics information.
Querying the current bus status
C13861
/ C14861 displays the bus status of the INTERBUS node:
Value
C13861/14861
[hex]
Bus status Description
0xyyy0 IBS-INIT Initialisation
0xyyy1 IBS-ACTIVE The bus is active. Data cycles are executed.
0xyyy2 IBS-READY The bus is ready for operation. No data cycles are executed.
yyy = device-internal use