13 Parameter reference
13.2 Parameters of the communication module for slot MXI1
60
Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C13881
C13885
C13892
Parameter | Name:
C13881 | Response time if the INTERBUS communication is interrupted
Data type: UNSIGNED_16
Index: 10694 = 0x29C6
If the "IBS-ACTIVE" status (INTERBUS is active and data is cyclically exchanged) is quit, the response parameterised
in C13880/1
is executed after the monitoring time set for the data exchange has elapsed.
A value of "65535" in this code deactivates the monitoring function.
A change in the monitoring is immediately effective.
Interruption of the INTERBUS communication
( 45)
Setting range (min. value | unit | max. value) Lenze setting
0 ms 65535 65535 ms
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13885 | Clear process data
Data type: UNSIGNED_8
Index: 10690 = 0x29C2
Setting which process data of the inverters are to be further processed for maintaining the internal communication
if the INTERBUS failed.
Selection list (Lenze setting printed in bold) Info
0 Use of the last master process data
1 Process data are set to the value '0'
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13892 | PCP data length
Data type: UNSIGNED_8
Index: 10683 = 0x29BB
Setting of the number of the parameter data words to be used (PCP)
The setting is activated ...
if all DIP switches (S205) are in the "OFF" position;
after executing the "11: Save start parameters" device command via standard device code C00002 and
performing another mains switching of the communication module/drive afterwards.
Setting the number of process data words
( 31)
Selection list (Lenze setting printed in bold) Info
0No PCB data
11 word
22 words
44 words
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT