34
SV01M
Commissioning
4.5.3 Advanced Setup Parameters
Code Possible Settings
IMPORTANT
No. Name Default Selection
Analog Inputs
Configuration
0 0 TB5: (0-10 VDC); TB25: (4-20mA)
1 TB5: (0 - 5 VDC); TB25: (4-20mA)
2 TB5: (2 - 10 VDC); TB25: (4-20mA)
4 TB5: (0-10 VDC); TB25: (0-20mA)
5 TB5: (0 - 5 VDC); TB25: (0-20mA)
6 TB5: (2 - 10 VDC); TB25: (0-20mA)
7
TB5 (0-10V) Analog
Input Monitoring
Action
0 0 No Action Selects the reaction to a loss of the 0-10V signal
at TB5
500ms is the minimum time above/below
Monitoring Level (P158) before triggering the
drive to trip or run at a preset speed.
For P157 = 3 or 6, the accel/decel time is set
in P786.
NOTE: P157 has priority over P163 and TB-13
presets/auto references (P121-P124)
1 If TB5 < P158 - Trip Fault F.FAU
2 If TB5 < P158 - Run Preset #8
3 If TB5 < P158 - Run Preset Seg. #16
4 If TB5 > P158 - Trip Fault F.FAU
5 If TB5 > P158 - Run Preset #8
6 If TB5 > P158 - Run Preset Seg. #16
TB5 (0-10V) Analog
Input Monitoring
Level (ML)
0.0 -10.0 {VDC} 10.0 Negative input voltage is not currently supported.
0-10V Analog Input
Deadband
0.0 0 {VDC} 10.0 Not active if [-10 to +10 VDC] option is selected.
P
Speed at Minimum
Signal
0.0 -999.0 {Hz} 1000
f
P161
P160
ref
10V
(20mA)
0V
(4mA)
V0111
P1
Speed at Maximum
Signal
60.0 -999.0 {Hz} 1000
NOTE
P160 sets the output frequency at 0% analog input
P161 sets the output frequency at 100% analog input
P160 or P161 < 0.0 Hz: For scaling purposes only; does not indicate opposite direction!
P160 > P161: Drive will react inversely to analog input signal
p1
Analog Input Filter 0.01 0.00 {s} 10.00 Adjusts the filter on the analog inputs (TB-5
and TB-25) to reduce the effect of signal noise
The P162 delay time will affect the response
time of diagnostic parameters (P520-P523).
P
TB-25 (4-20mA)
Analog Input
Monitoring Action
0 0 No Action Selects the reaction to a loss of the 4-20 mA
signal at TB-25.
Signal is considered lost if it falls below the
value set in P164
Digital outputs can also indicate a loss of 4-20
mA signal; see P140, P142
For P163 = 3 or 6, the accel/decel time is
set in P781.
NOTE: P163 has priority over TB-13 presets/auto
references (P121-P124)
1 If TB25 < P164 - Trip Fault
2 If TB25 < P164 - Run Preset #7
3 If TB25 < P164 - Run Preset Seg. #15
4 If TB25 > P164 - Trip Fault
5 If TB25 > P164 - Run Preset #7
6 If TB25 > P164 - Run Preset Seg. #15