42
SV01M
Commissioning
4.5.6 Network Parameters
Code Possible Settings
IMPORTANT
No. Name Default Selection
Network Protocol 0 Not Active This parameter setting is based upon the network
or I/O module that is installed.
1 Remote Keypad
2 Modbus RTU
3 CANopen
4 DeviceNet
5 Ethernet
6 Profibus
7 Lecom-B
8 I/O Module
Module Type Installed 0 0 No Module Installed Module type format: 0xAABC; Drive Display:
AA.B.C
AA = Module Type
B = Major revision
C = minor revision
1 Basic I/O (0x0100, 1.0.0)
2 RS485/Rem. Keypad (0x0200, 2.0.0)
3 CANopen (0x0300, 3.0.0)
11 PROFIBUS (0x1100, 11.0.0)
12 Ethernet (0x1200, 12.0.0)
Module Status 0 0 Not Initialized
1 Initialization: Module to EPM
2 Initialization: EPM to Module
3 Online
4 Failed Initialization Error
5 Time-out Error
6 Initialization Failed Module type mismatch P401
7 Initialization Error Protocol selection mismatch P400
Module Reset 0 0 No Action Returns module parameters 401…499 to the
default values shown in the manual
1 Reset parameters to default values
Module Timeout Action 3 0 No Fault Action to be taken in the event of a Module/
Drive Time-out.
Time is fixed at 200ms
STOP is by the method selected in P111.
1 STOP (see P111)
2 Quick Stop
3 Fault (F_ntF)
Current Network Fault 0 No Fault
1 F.nF1 NetIdle Mode
2 F.nF2 Loss of Ethernet I/O connection
3 F.nF3 Network Fault
4 F.nF4 Explicit Message Timeout
5 F.nF5 Overall Network Timeout
6 F.nF6 Overall Explicit Timeout
7 F.nF7 Overall I/O Message Timeout
Proprietary Manufacturer specific
7
Module Specific Parameters
Refer to the Communications Reference Guide
specific to the network or I/O module installed.