Electrical installation
Wiring of system bus (CAN)
5
122
EDKCSEX064 DE/EN/FR 6.0
Bus cable length
Note!
The permissible cable lengths must be observed.
1. Check the compliance with the total cable length in Tab. 5−1.
The baud rate determines the total cable length.
CAN baud rate [kbit/s] Max. bus length [m]
50 1500
125 630
250 290
500 120
1000 25
Tab. 5−1 Total cable length
2. Check the compliance with the segment cable length in Tab. 5−2.
The segment cable length is determined by the cable cross−section used and the
number of nodes. Without a repeater, the segment cable length corresponds to
the total cable length.
Number of nodes
Cable cross−section
0.25 mm
2
0.5 mm
2
0.75 mm
2
1.0 mm
2
2 240 m 430 m 650 m 940 m
5 230 m 420 m 640 m 920 m
10 230 m 410 m 620 m 900 m
20 210 m 390 m 580 m 850 m
32 200 m 360 m 550 m 800 m
63 170 m 310 m 470 m 690 m
Tab. 5−2 Segment cable length
3. Compare the two values detected.
If the value detected from Tab. 5−2 is smaller than the total cable length to be
provided from Tab. 5−1 , repeaters must be used. Repeaters divide the total cable
length into segments.
Operating instructions for ECS axis module
Here you can find detailed information on how to use repeaters.

Table of Contents

Other manuals for Lenze ECSEM Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze ECSEM Series and is the answer not in the manual?

Lenze ECSEM Series Specifications

General IconGeneral
BrandLenze
ModelECSEM Series
CategoryControl Unit
LanguageEnglish

Related product manuals