Troubleshooting and fault elimination
?
?
MA DrivePLC DE/EN/FR 1.0
17
Display RemedyCauseError
keypad PC
1)
EF
a
63
Communication error to
CAN-IN2
CAN-IN2-object receives faulty data
or communication is interrupted
l
Plug-in connection - bus module
Ø
Check FIF
l
Check transmitter
l
Increase monitoring time under
C0357/2 if necessary
EF
a
64
Communication error to
CAN-IN1 with event or time control
CAN-IN1-object receives faulty data
or communication is interrupted
l
Plug-in connection - bus module
Ø
Check FIF
l
Check transmitter
l
Increase monitoring time under
C0357/3 if necessary
EF
a
65
BUS-OFF
(many communication errors
occurred)
The Drive PLC has received too
many incorrect telegrams via the
system bus and has been
disconnected
l
Check whether bus terminator
available
l
Shield control of the cables
l
Check PE connection
l
Check bus load, if necessary,
reduce the baud rate
((
a
91
External fault (TRIP-Set) A digital signal assigned to TRIP set
has been activated
Check external encoder
+
a
105
Internal fault Contact Lenze
PF
a
74
Fault in program execution A fault was detected in the program. Send the Drive PLC with the data
set (on diskette) to Lenze.
PJ
a
79
Initialisation error during transfer of
parameter set
l
A fault was detected during the
transfer of the parameter set to
the Drive PLC.
l
Parameter set does not match
Drive PLC
Correct the parameter set.
3
a
75
Internal fault Contact Lenze
3
a
72
Wrong PAR1 transfer when using
the keypad/PC.
PAR1 is defective. Repeat data transfer or load Lenze
settings
3
a
79
Internal fault Contact Lenze
1)
LECOM fault number