Questions and Answers

  • C
    Christopher EvansAug 31, 2025
    What does earth fault mean on Lenze ESMD552L4TXA?
    • J
      Jacob MckeeAug 31, 2025
      If the Lenze Inverter indicates an earth fault, it could be due to: * A grounded motor phase: Inspect the motor and motor cable. * Excessive capacitive charging current of the motor cable: Use shorter motor cables with a lower charging current.
  • F
    Frank SchultzAug 25, 2025
    Why Lenze DC Drives show earth fault?
    • R
      Robert SpenceAug 25, 2025
      An earth fault in Lenze DC Drives can occur if a motor phase is grounded, so you should check the motor and motor cable. It can also be due to excessive capacitive charging current of the motor cable, in this case use shorter motor cables with lower charging current.
  • S
    stephanieliuAug 25, 2025
    What to do if Lenze DC Drives have controller overtemperature?
    • S
      Stephen AcostaAug 26, 2025
      If the controller has an overtemperature, it means the controller is too hot inside. To resolve this, reduce the controller load and improve cooling.
  • T
    Travis JonesAug 26, 2025
    What to do if Lenze DC Drives show undervoltage on DC bus?
    • K
      Katrina DawsonAug 26, 2025
      If Lenze DC Drives show undervoltage on the DC bus, it could be because the mains voltage is too low. Check the mains voltage.
  • R
    Rita CantrellAug 27, 2025
    How to resolve dynamic braking fault in Lenze DC Drives?
    • J
      johnsonthomasAug 27, 2025
      A dynamic braking fault in Lenze DC Drives typically means that the dynamic braking resistors are overheating. To resolve this, increase the deceleration time.
  • J
    Joe VargasAug 27, 2025
    What to do if Lenze DC Drives have a single phase fault?
    • M
      Michaela AllenAug 27, 2025
      If Lenze DC Drives have a single phase fault, it means a mains phase has been lost. Check the mains voltage.
  • K
    Kristine MeyerAug 28, 2025
    What to do if Lenze DC Drives have a communication error?
    • D
      dawnporterAug 28, 2025
      If Lenze DC Drives have a communication error, it may be because the serial timer has timed out. Check the serial link connections.
  • W
    Whitney LewisAug 29, 2025
    What to do if Lenze ESMD552L4TXA shows short-circuit or overload?
    • E
      Evan BerryAug 29, 2025
      If the Lenze Inverter experiences a short-circuit or overload, there are several potential causes: * A short-circuit itself: Investigate the cause and inspect the motor cable. * Excessive capacitive charging current: Use shorter motor cables. * Acceleration time is too short: Increase the acceleration time and check the controller selection. * Defective motor cable: Check the wiring. * Internal fault in the motor: Check the motor. * Frequent and long overload: Check controller selection.
  • B
    Beth RossAug 29, 2025
    Why is my Lenze Inverter showing overvoltage on DC bus?
    • Q
      qweeksAug 29, 2025
      If your Lenze Inverter is experiencing an overvoltage on the DC bus, it could be due to several reasons: * The mains voltage might be too high: Verify the mains voltage. * The deceleration time might be excessively short, or the motor might be in generator mode: Increase the deceleration time or consider using a dynamic braking option. * Earth leakage on the motor side: Check the motor and motor cable, separating the motor from the controller to diagnose.
  • R
    Ronald RobertsAug 30, 2025
    What causes motor overload on Lenze ESMD552L4TXA?
    • J
      Jeremiah JonesAug 30, 2025
      If the Lenze Inverter displays a motor overload (I2t overload), it means the motor is thermally overloaded. This can be due to: * Impermissible continuous current. * Frequent or excessively long acceleration processes. To resolve this: * Check the controller selection. * Check the setting of c20.

Summary

Safety Information and Precautions

General Safety Guidelines

General safety precautions and responsibilities for personnel.

Intended Use and Compliance

Guidelines for intended use and compliance with directives like Machinery and EMC.

Installation Safety

Precautions for handling, avoiding mechanical stress, and electrostatic discharge.

Electrical Connection Safety

Requirements for electrical installation, national regulations, and EMC considerations.

Safe Operation Practices

Requirements for monitoring, protection devices, and safe operation practices.

Explosion Proof Application Policy

Policy and liability statement regarding explosion proof motors and inverter use.

UL System Safety Notes

Notes specific to UL systems, including branch circuit protection and wiring.

Technical Specifications

Standards and Application Conditions

Overview of conformity, approvals, and environmental conditions for operation.

Device Ratings and Specifications

Detailed specifications for power, voltage, current, and frequency ratings.

Installation Procedures

Electrical Installation Guidelines

Instructions for connecting the drive electrically, including EMC.

Control Terminal Functions

Detailed description of each control terminal and its function.

Commissioning and Setup

Troubleshooting and Fault Diagnosis

Error Code Troubleshooting

Detailed explanation of error codes, their causes, and corrective actions.

Short-Circuit and Overload Faults

Troubleshooting steps for OC1 short-circuit or overload errors.

Earth Fault Troubleshooting

Troubleshooting steps for OC2 earth fault errors.

Motor Overload Faults (OC6)

Troubleshooting steps for OC6 motor overload errors, including UL delay.

Lenze ESMD552L4TXA Specifications

General IconGeneral
TypeInverter
Power Rating5.5 kW
Input Voltage380-480 V AC
Output Voltage0-480 V AC
Input Current12 A
Output Current12 A
SeriesESMD
Protection ClassIP20
Communication InterfaceCANopen
Cooling MethodFan
Operating Temperature-10 ... 40 °C
Storage Temperature-25 ... 70 °C
Relative Humidity5% to 95% (non-condensing)
Control MethodVector Control