14 Lenze 13466184 EDBSL03 v20 EN, DE, FR, IT, ES
Code Possible Settings
IMPORTANT
No. Name
Lenze
Selection
CE1
Conguration -
Digital input E1
1 1 Activate xed setpoint 1 (JOG1)
• Use C37...C39 to adjust xed setpoints
• Activate JOG3: Both terminals =
HIGH
2 Activate xed setpoint 2 (JOG2)
3 DC braking (DCB) See also C36
4 Direction of rotation LOW = CW rotation
HIGH = CCW rotation
5 Quick stop Controlled deceleration to standstill,
active LOW; Set decel rate in C13 or
c03
CE2
Conguration -
Digital input E2
4 6 CW rotation
7 CCW rotation
CW rotation = LOW and CCW rotation =
LOW: Quick stop; Open-circuit protected
8 UP (setpoint ramp-up) UP = LOW and DOWN = LOW: Quick
stop; Use momentary NC contacts
9 DOWN (setpoint ramp-down)
10 TRIP set
Active LOW, triggers EEr (motor coasts
to standstill)
NOTE: NC thermal contact from the
motor can be used to trigger this input
CE3
Conguration -
Digital input E3
3 11 TRIP reset See also c70
12 Accel/decel 2 See c01 and c03
13 Deactivate PI Disables PI function for manual control
14 Activate xed PI setpoint 1 • Use C37...C39 to adjust xed
setpoints
• Activate xed PI setpoint 3: Both
terminals = HIGH
15 Activate xed PI setpoint 2
Note
A CFG fault will occur under the following conditions:
• E1...E3 settings are duplicated (each setting can only be used once)
• One input is set to UP and another is not set to DOWN, or vice-versa
C08
Conguration -
Relay output
1 Relay is energized if
0 Ready
1 Fault
2 Motor is running
3 Motor is running - CW rotation
4 Motor is running - CCW rotation
5 Output frequency = 0 Hz
6 Frequency setpoint reached
7 Threshold (C17) exceeded
8 Current limit (motor or generator
mode) reached
9 Feedback within min/max alarm
(d46, d47) range
10 Feedback outside min/max alarm
(d46, d47) range
C09
Network address 1 1 247 Each controller on network must have
unique address