16 Lenze 13466184 EDBSL03 v20 EN, DE, FR, IT, ES
Commissioning
Code Possible Settings
IMPORTANT
No. Name
Lenze
Selection
C31
Analog input dead
band
0 0 Enabled C31 = 0 activates dead band for analog
input. When analog signal is within dead
band, controller’s output = 0.0 Hz and
display will read StP
1 Disabled
C34
Conguration -
analog input
0 0 0...10 V
1 0...5 V
2 0...20 mA
3 4...20 mA
4 4...20 mA monitored
Will trigger SD5 fault if signal falls below
2 mA
C36
Voltage - DC
injection brake
(DCB)
4.0 0.0 {%} 50.0 See CE1...CE3 and c06
Conrm motor suitability for use with
DC braking
C37
Fixed setpoint 1
(JOG 1)
20.0 0.0 {Hz} 999 When PI is active (see d38), C37...C39
are xed PI setpoints
C38
Fixed setpoint 2
(JOG 2)
30.0 0.0 {Hz} 999
C39
Fixed setpoint 3
(JOG 3)
40.0 0.0 {Hz} 999
C46
Frequency setpoint 0.0 {Hz} 500 Display: Setpoint via analog input,
function UP/DOWN, or LECOM
C50
Output frequency 0.0 {Hz} 500 Display
C53
DC bus voltage 0.0 {%} 255 Display
C54
Motor current 0.0 {%} 255 Display
C59
PI feedback c86 {%} c87 Display
C70
Proportional gain 5.0 0.0 {%} 99.9
C71
Integral gain 0.0 0.0 {s} 99.9
C90
Input voltage
selection
0 Auto Automatically sets to Low (1) or High
(2) upon next power-up, depending on
input voltage
1 Low For 200 V or 400 V input
2 High For 240 V or 480 V input
Note
To simplify commissioning, the Lenze setting is preset at the factory, depending
on model:
C90 = 1 for 400/480 V models
C90 = 2 for 230/240 V models
Upon reset (C02 = 1, 2), C90 = 0. Conrm correct setting after next power-up.
C94
User password 0 0 999
Changing from “0” (no password),
value will start at 763
When set to a value other than 0,
must enter password at C00 to access
parameters
C99
Software version Display, format: x.yz
c01
Acceleration time 2 5.0 0.0 {s} 999 Activated using CE1...CE3
c01 = frequency change 0 Hz...C11
c03 = frequency change C11...0 Hz
• For S-ramp accel/decel, adjust c82
c03
Deceleration time 2 5.0 0.0 {s} 999