18 Lenze 13466184 EDBSL03 v20 EN, DE, FR, IT, ES
Commissioning
Code Possible Settings
IMPORTANT
No. Name
Lenze
Selection
c25
Serial baud rate 0 0 LECOM: 9600 bps
Modbus: 9600,8,N,2
See C01
LECOM if C01 = 0...3
Modbus if C01 = 8...11
1 LECOM: 4800 bps
Modbus: 9600,8,N,1
2 LECOM: 2400 bps
Modbus: 9600,8,E,1
3 LECOM: 1200 bps
Modbus: 9600,8,O,1
c38
Actual PI setpoint c86 c87 Display
c40
Frequency setpoint
via keys
or Modbus
0.0 0.0 {Hz} 500 Only active if C01 is set properly
(C01 = 1,5,7,9,11)
c42
Start condition
(with mains on)
1 0 Start after LOW-HIGH change at
terminal 28
See also c70
1 Auto start if terminal 28 = HIGH
WARNING!
Automatic starting/restarting may cause damage to equipment and/or injury to
personnel! Automatic starting/restarting should only be used on equipment that is
inaccessible to personnel.
c60
Mode selection for c61
0 0 Monitoring only
c60 = 1 allows the keys to adjust
speed setpoint (c40) while monitoring c61
1 Monitoring and editing
c61
Present status/error status/error message Display
Refer to Section 5 for explanation of
status and error messages
c62
Last error error message
c63
Last error but one
c70
Conguration TRIP
reset (error reset)
0 0 TRIP reset after LOW-HIGH
change at terminal 28, mains
switching, or after LOW-HIGH
change at digital input “TRIP reset”
1 Auto-TRIP reset Auto-TRIP reset after the time set in
c71
More than 8 errors in 10 minutes will
trigger rSt fault
WARNING!
Automatic starting/restarting may cause damage to equipment and/or injury to
personnel! Automatic starting/restarting should only be used on equipment that is
inaccessible to personnel.
c71
Auto-TRIP reset delay 0.0 0.0 {s} 60.0 See c70
c78
Operating time
counter
Display
Total time in status “Start”
0...999 h: format xxx
1000...9999 h: format x.xx (x1000)
10000...99999 h: format xx.x (x1000)
c79
Mains connection
time counter
Display
Total time of mains = on
c81
PI setpoint 0.0 c86 c87
c82
S-ramp integration
time
0.0 0.0 {s} 50.0 c82 = 0.0: Linear accel/decel ramp
c82 > 0.0: Adjusts S-ramp curve for
smoother ramp
c86
Minimum feedback 0.0 0.0 999 Select feedback signal at C34
If feedback is reverse-acting, set
c86>c87
c87
Maximum feedback 100 0.0 999