I/O data transfer (implicit messages)
I/O configuration with »RSLogix 5000« version 20 or higher
66
Lenze · Decentralised frequency inverter 8400 motec (EtherNet/IP™ option) · EDS84DMOTEIP EN 3.0 - 02/2019
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
8. Go to the "Module Definition" dialog window and make the connection settings.
The terms "input" and "output" refer to the point of view of the scanner:
Assembly input objects (input) are sent from the adapter to the scanner.
Assembly output objects (output) are sent from the scanner to the adapter.
Settings for Lenze technology applications or user-definable parameter sets:
Select "Exclusive Owner - Custom" connection.
If you use the Lenze technology applications or user-definable parameter sets in the
inverter, the "Exclusive Owner - Custom" assembly object instance always has to be
selected.
•Set Data type = INT.
The INT data type is exchanged via ports MCI_IN and MCI_OUT of the Inverter Drive
8400 motec. The SINT data type requires an additional PLC logic for the conversion.
For the "Exclusive Owner - Custom" connection: set input = 8, output = 10.
For "Exclusive Owner - AC Drive ..." connections: set input = 3, output = 3.
•SetTag Suffix = 1.
A tag suffix formulates a module-describing tag name.