I/O data transfer (implicit messages)
I/O configuration with »RSLogix 5000« version 20 or higher
66
Lenze · Decentralised frequency inverter 8400 motec (EtherNet/IP™ option) · EDS84DMOTEIP EN 3.0 - 02/2019
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
8. Go to the "Module Definition" dialog window and make the connection settings.
The terms "input" and "output" refer to the point of view of the scanner:
• Assembly input objects (input) are sent from the adapter to the scanner.
• Assembly output objects (output) are sent from the scanner to the adapter.
Settings for Lenze technology applications or user-definable parameter sets:
• Select "Exclusive Owner - Custom" connection.
If you use the Lenze technology applications or user-definable parameter sets in the
inverter, the "Exclusive Owner - Custom" assembly object instance always has to be
selected.
•Set Data type = INT.
The INT data type is exchanged via ports MCI_IN and MCI_OUT of the Inverter Drive
8400 motec. The SINT data type requires an additional PLC logic for the conversion.
For the "Exclusive Owner - Custom" connection: set input = 8, output = 10.
For "Exclusive Owner - AC Drive ..." connections: set input = 3, output = 3.
•SetTag Suffix = 1.
A tag suffix formulates a module-describing tag name.