Lenze · Decentralised frequency inverter 8400 motec (EtherNet/IP™ option) · EDS84DMOTEIP EN 3.0 - 02/2019 79
Diagnostics
LED status displays
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
11 Diagnostics
EtherNet/IP communication can be diagnosed via the LEDs of the Communication Unit. Moreover,
the »Engineer« serves to show diagnostic information.
11.1 LED status displays
E84DG056
LED Colour / Status Description
MS green red
Off Off CIP module status: "Nonexistent"
The Communication Unit is not supplied with voltage.
Off On
CIP module status: "Major Unrecoverable Fault"
The Communication Unit has an unrecoverable fault.
Off blinking
CIP module status: "Major Recoverable Fault"
The Communication Unit has a recoverable fault.
On Off
CIP module status: "Operational"
The Communication Unit is working correctly.
blinking Off
CIP module status: "Standby"
The communication unit is not fully configured yet or the configuration
is erroneous (e.g. invalid IP address).
blinking blinking
CIP module status: "Device Self Testing"
The Communication Unit performs a self-test.
250 ms
250 ms
250 ms
250 ms
250 ms
250 ms