EasyManua.ls Logo

Lenze EtherNet/IP E84DGFCGFNP - Monitoring; Fault with regard to EtherNet;IP communication

Lenze EtherNet/IP E84DGFCGFNP
149 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Monitoring
78 Lenze · Decentralised frequency inverter 8400 motec (EtherNet/IP™ option) · EDS84DMOTEIP EN 3.0 - 02/2019
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
10 Monitoring
Fault with regard to EtherNet/IP communication
The response of the Inverter Drive 8400 motec to a fault with regard to EtherNet/IP communication
can be set in the »Engineer« under the Monitoring tab.
Settings Description
Idle Mode The 32-bit real time header sent by the scanner is evaluated.
Run/idle flag (bit 0) = 1:
The scanner indicates the validity of the I/O data.
Run/idle flag (bit 0) = 0:
The I/O data are invalid and the response parameterised here (C13880/
1) is executed on the inverter.
The I/O data are processed as set in (C13885
).
Overall Ethernet
Communication Timeout
If, after the time set in (C13881
) has elapsed, access via the »Engineer«
is no longer executed, the response parameterised here (C13880/4
) will be
effected in the inverter.
Fault Mode The adapter (Communication Unit) monitors the I/O connection to the
scanner.
If no "implicit message" has been received within the timeout time for
implicit messages parameterised by the scanner, the response
parameterised here (C13880/2
) is executed on the inverter.
Overall Ethernet Timeout Time Here, the overall message timeout time (C13881
) is set.
If no message has been received within this time, the response
parameterised in (C13880/4
) is executed.
The following messages are monitored:
Implicit messages
Explicit messages
»Engineer« access via EtherNet/IP
Explicit Msg Timeout If no "explicit message" has been received within the timeout time for
explicit messages parameterised by the scanner, the response
parameterised here (C13880/3
) is executed on the inverter.
Clear I/O Data (C13885
), serves to set the I/O data to be processed by the adapter to
maintain internal communication if ...
the CIP network status (C13862
) of the controlling I/O connection is not
"Connected" or
an idle event has occurred.

Table of Contents

Related product manuals