Technical Data
821XKlimaBA0399 3-5
3.3 Rated data (Operation with 150 % overload)
Operation permitted with a mains voltage of
3AC / 400 V - 460V / 50/60 Hz
3.3.1 Types 8211 to 8214
150 % overload Type 8211 8212 8213 8214
Mains voltage V
rated
[V] 320V- 0%
$
V
rated
$
510V+ 0%; 45Hz
¡
65Hz
á
0%
Alternative DC supply V
DC
[V] 450 V - 0%
$
V
DC
$
715 V + 0%
Mains current
with mains filter/mains choke
without mains filter/mains choke
I
mains
[A]
I
mains
[A]
2.5
3.75
3.9
5.85
5.0
7.5
7.0
--
Data for mains operation with 3 AC/400 V/50 Hz/60 Hz; 450 V
$
V
DC
$
620 V or
3 AC/460 V/50 Hz/60 Hz; 460 V
$
V
DC
$
725 V 400V 460V 400V 460V 400V 460V 400V 460V
Motor power (4 pole ASM)
P
rated
[kW] 0.75 1.1 1.5 1.5 2.2 2.2 3.0 3.7
off 4kHz/8kHz*
P
rated
[hp] 1.0 1.5 2.0 2.0 2.9 2.9 4.0 5.0
Output power U, V, W
off 4 kHz/8 kHz*
S
rated8
[kVA] 1.6 1.9 2.7 3.1 3.8 4.3 5.2 5.8
Output power +U
G
,-U
G
1)
P
DC
[kW] 0.7 0.7 0.0 0.0 1.0 1.0 0.0 0.0
4kHz* I
rated4
[A] 2.4 2.4 3.9 3.9 5.5 5.5 7.3 7.3
8kHz* I
rated8
[A] 2.4 2.4 3.9 3.9 5.5 5.5 7.3 7.3
12 kHz* I
rated12
[A] 2.0 1.9 3.3 3.0 4.6 4.3 6.1 5.7
16 kHz* I
rated16
[A] 1.8 1.7 2.9 2.7 4.1 3.8 5.5 5.1
noise optimized 4 kHz* I
rated4
[A] 2.4 2.3 3.9 3.7 5.5 5.2 7.3 6.9
noise optimized 8 kHz* I
rated8
[A] 2.1 2.0 3.4 3.2 4.7 4.5 6.3 6.0
noise optimized 12 kHz* I
rated12
[A] 1.9 1.8 3.1 2.9 4.4 4.1 5.8 5.4
noise optimized 16 kHz* I
rated16
[A] 1.6 1.5 2.5 2.3 3.6 3.3 4.7 4.4
Max.
4kHz* I
rated max4
[A] 3.6 3.6 5.9 5.9 8.3 8.3 11.0 11.0
output
8kHz* I
rated max8
[A] 3.6 3.6 5.9 5.9 8.3 8.3 11.0 11.0
for
12 kHz* I
rated max12
[A] 3.0 2.8 4.9 4.6 6.9 6.6 9.2 8.7
60s
2)
16 kHz* I
rated max16
[A] 2.7 2.5 4.4 4.1 6.2 5.8 8.2 7.7
noise optimized 4 kHz* I
rated max4
[A] 3.6 3.7 5.9 5.6 8.3 7.8 11.0 10.4
noise optimized 8 kHz* I
rated max8
[A] 3.1 2.9 5.1 4.8 7.1 6.7 9.4 8.9
noise optimized 12 kHz* I
rated max12
[A] 2.9 2.7 4.7 4.4 6.6 6.2 8.8 8.2
noise optimized 16 kHz* I
rated max16
[A] 2.4 2.1 3.8 3.5 5.4 5.0 7.1 6.6
Power loss (Operation with I
rated
) P
v
[W] 55 75 90 100
* No dynamic chopper-frequency lowering of the inverter
For all other data see chapter 3.2.2.