Technical Data
3-6 821XKlimaBA0399
3.3.2 Types 8215 to 8218
150 % overload Type 8215 8216 8217 8218
Mains voltage V
rated
[V] 320V- 0%
$
V
rated
$
510V+ 0%; 45Hz
¡
65Hz
á
0%
Alternative DC supply V
G
[V] 450V- 0%
$
V
DC
$
715V+ 0%
Mains current
with mains filter/mains choke
without mains filter/mains choke
I
mains
[A]
I
mains
[A]
8.8
13.2
12.0
18.0
15.0
22.5
20.5
--
Data for mains operation with3 AC/400V/50 Hz/60 Hz; 450V
$
V
DC
$
650Vor
3 AC/460V/50 Hz/60Hz; 460V
$
V
DC
$
725V 400V 460V 400V 460V 400V 460V 400V 460V
Motor power (4 pole ASM)
P
rated
[kW] 4.0 5.5 5.5 7.5 7.5 11.0 11.0 15.0
off 4kHz/8kHz*
P
rated
[hp] 5.4 7.5 7.5 10.0 10.0 15.0 15.0 20.0
Output power U, V, W
off 4 kHz/8 kHz*
S
rated8
[kVA] 6.5 7.5 9.0 10.3 11.4 13.7 16.3 19.5
Output power +U
G
,-U
G
1)
P
DC
[kW] 1.0 1.0 0.0 0.0 3.9 3.9 0.0 0.0
Output
4kHz* I
rated4
[A] 9.4 9.4 13.0 13.0 16.5 16.5 23.5 23.5
current
8kHz* I
rated8
[A] 9.4 9.4 13.0 13.0 16.5 16.5 23.5 23.5
12 kHz* I
rated12
[A] 7.9 7.4 10.9 10.3 13.9 13.0 19.7 18.5
16 kHz* I
rated16
[A] 7.0 6.6 9.7 9.1 12.3 11.6 17.6 16.5
noise optimized
4kHz*
I
rated4
[A] 9.4 8.9 13.0 12.3 16.5 15.6 23.5 22.1
noise optimized
8kHz*
I
rated8
[A] 8.0 7.6 11.1 10.5 14.1 13.3 20.0 18.8
noise optimized
12 kHz*
I
rated12
[A] 7.5 7.0 10.4 9.7 13.2 12.4 18.8 17.6
noise optimized
16 kHz*
I
rated16
[A] 6.1 5.6 8.4 7.8 10.7 9.9 15.3 14.1
4kHz* I
rated max4
[A] 14.1 14.1 19.5 19.5 24.8 24.8 35.3 35.3
8kHz* I
rated max8
[A] 14.1 14.1 19.5 19.5 24.8 24.8 35.3 35.3
12 kHz* I
rated max12
[A] 11.9 11.1 16.4 15.4 20.8 19.6 29.6 27.9
16 kHz* I
rated max16
[A] 10.6 9.8 14.6 13.6 18.6 17.4 26.5 24.7
noise optimized
4kHz*
I
rated max4
[A] 14.1 13.3 19.5 18.3 24.8 23.4 35.3 55.1
noise optimized
8kHz*
I
rated max8
[A] 12.0 11.3 16.6 15.6 21.1 19.9 30.0 28.2
noise optimized
12 kHz*
I
rated max12
[A] 11.3 10.6 15.6 14.6 19.8 18.8 28.2 26.4
noise optimized
16 kHz*
I
rated max16
[A] 9.1 8.5 12.7 11.7 16.1 14.9 22.9 21.1
Power loss
(Operation with I
rated
)
P
v
[W] 150 200 280 400
* No dynamic chopper-frequency lowering of the inverter
For all other data see chapter 3.2.3.
1)
This power can be additionallyobtained when operating a matching motor
2)
The currents applyto a periodical load cycle with 1 minute overcurrent with the current mentioned here
and 2 minutes base load with75%I
Nx
.