Installation
821XKlimaBA0399 4-13
Terminal Use
(Factory setting is printed in bold)
Level Data
Analog
7 GND 1
8 Setpoint input,
reference:
Te rmi na l 7
(0 to 10V)
6
4
2
5-6
5-6
3-4
1-2
0to20mA
4to20mA
0to5V
0to10V
Resolution: 820X: 9 bit,
821X/822X/824X: 10 bit
Resolution: 9 bit
Resolution: 10 bit
Linearityfault:
0.5 %
Temperature fault: 0.3 %
(0...+40
C)
Jumper
Input resistance
Voltage signal: > 100 k
Current signal: 250
9 Supply for setpoint potentiometer 5.2V / 6mA
Analog
output
62 Analog output, reference: terminal 7
0 ... 6V
(Changes possible under C108)
0... 6 V/
2mA
Resolution: 820X: 8 bit
821X/822X/824X: 10 bit
Resolution: 8 bit
Resolution: 10 bit
Digital
inputs
20 Voltage supply for digital inputs
820X: 12 V/20 mA
821X/822X/824X: 15 V/20 mA
12 V/20 mA
15 V/20 mA
28 Controller enable HIGH
HIGH: 12 V... 30 V
E4 CW rotation/
CCW rotation (CW/CCW)
CW: LOW
CCW: HIGH
LOW:0V...3V
E3 DC-injection brake HIGH
E2
JOG frequencies
Binary code
E1
20Hz, 30Hz, 40Hz
39 GND2 (reference for external voltages)
Terminal Use
(Factory setting is printed in bold)
Relay position
(switched)
Data
Rela y
output
K11 Relay output normally-closed contact
(TRIP)
opened
24 V AC / 3,0 A or
60 V DC / 0.5 A
K1
K22 Relay mid-position contact
K24 Relay output normally-open contact
(TRIP)
closed