Configuration
821XKlimaBA0399 7-3
Code Name Possible settings IMPORTANT
Lenze Selection Info
C001
¤
Operating mode -0- -0- Setpoint selection via term. 8
Control via terminals
Parameter setting via 8201BB
-1- Setpoint selection via 8201BB or via
LECOM
Control via terminals
Parameter setting via 8201BB
-2- Setpoint selection via term. 8
Control via terminals
Parameter setting via LECOM
-3- Setpoint selection via LECOM
Control via LECOM
Parameter setting via LECOM
[C002
]*
Parameter set -0- -0- Function executed
-1- Overwrite PAR1 with factory setting
-2- Overwrite PAR2 with factory setting
-3- Overwrite PAR1 and PAR2 with the data of
the operating module
-4- Overwrite PAR1 with the data of the
operating module
-5- Overwrite PAR2 with the data of the
operating module
-6- Transmit PAR1 and PAR2 to the operating
module
-7- Overwrite PAR1, PAR2 and the
unit-dependent data (C016, C036, C088,
C091)with the data of the operating
module.
C003
¤
Save parameter
set
-1- -0- Data will not be saved on EEPROM; all data
will be lost when switching off the mains
-1- Data will be saved on EEPROM; setting
when switching on the mains
-0- only valid for
C010, C011,
C012, C013,
C037, C038,
C105, C181 and
C182
C004
¤
Switch-on display -0- -0- Field frequency f
d
-1- Unit load
-2- Motor current